Your questions answered: Next-generation lighting: the emergence of PoE for lighting and controls

Your questions answered: Next-generation lighting: the emergence of PoE for lighting and controls.

09/28/2016


John Casadonte, Product Marketing Manager, Cree Inc.Using Power over Ethernet (PoE) not only cuts installation and commissioning costs, but—more importantly—opens the door to endless building integration options that build upon the idea of intelligent or high-performance buildings. Read answers to questions that were not addressed in the live Sept. 20, 2016, webcast Next-generation lighting: the emergence of PoE for lighting and controls.

Question: Do you have case studies that compare a typical office building with fluorescent lamps versus an “equivalent” power over Ethernet (PoE) application?

John Casadonte: Please see this Quest case study for an example.

Question: What is the 90 W standard distance limitation?

Casadonte: 100 meters.

Question: What is the current technology maximum for a PoE wattage available on a given category cable for a lighting fixture?

Casadonte: A little over 100 W as the Cat-x will likely begin to overheat if pushed further. Expectations that new cable technology will be in place as the PoE standards grow.

Question: NFPA 70: National Electrical Code (NEC) requires complete separation of wiring for emergency lighting circuits. How do you configure your system to provide separation of normal power lighting from emergency?

Casadonte: A separate PoE switch and Cat-x cabling.

Question: How do we guard against obsolescence in cabling when Cat-8 is already on the horizon?

Casadonte: A tough question to address. Historically most data vendors have handled product/technology very gracefully, but we are now facing a tremendously fast ramp-up and it is likely some investments today may be lost as time progresses.

Question: Are the PoE lighting devices more energy efficient than their 120/277 V equivalents? That is comparing LED to LED.

Casadonte: About the same.

Question: Will the egress lighting/emergency be color indicating?

Casadonte: All depends on the luminaire. Speaking specifically on our Cree portfolio, we have field changeable color temperatures. In our case, the answer is yes.


<< First < Previous Page 1 Page 2 Page 3 Page 4 Next > Last >>

Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me