Natatorium Design Saves Space and Money

Staff -- Consulting-Specifying Engineer, 12/1/2000

The new 85,000-square-foot Oak Point recreation center in Plano proves the old adage that everything is bigger in Texas. However, thanks to new technology and natatorium design concepts, designers managed to make the pool equipment room for the complex's 50-meter indoor pool significantly smaller than a typical natatorium.

The heating, ventilating and air-conditioning system and other innovative proposals from the design team saved approximately $38,000 on the $13 million project. Much of the credit goes to the project's design consortium: Brinkley Sargent Architects, Dallas; G and S Consulting Engineers LLC, Dallas; and H and G Systems, Garland, Texas.

The consortium specified a newly developed swimming pool dehumidifier, and by eliminating the need for conventional swimming pool water heaters, the chosen equipment saved several hundred square feet of space in the pool equipment room.

Dehumidifier/boiler combination

A natatorium of this size typically uses dehumidifiers to remove moisture from the air and sometimes to recover energy to heat the pool water. Large boilers are usually required as primary heaters, backup heaters or secondary-stage heaters during dump/fill periods.

At Oak Point, however, two rooftop dehumidifiers are fitted with modular gas boilers totaling 1.5 million British thermal units. The dehumidifiers keep the space dry and recover enough energy to heat the main pool's 624,000 gallons and the adjoining leisure pool's 48,000 gallons of water to 82°F. An on-board glycol-to-water heat exchanger provides supplemental or backup heating, if needed, from a glycol loop connected to the boilers. The boiler/glycol-loop combination is also responsible for heating the 30,000-square-foot indoor pool area to 84°F via an additional on-board water-to-air heat exchanger.

Air distribution

Instead of a single return-air wall diffuser, the design team proposed a system in which return air is handled by 20 18-inch spiral aluminum ducts along the pool's exterior wall that drop down to 12 inches above the pool deck. To further improve air distribution, each duct has a balancing damper.

"We think this is the better way to handle return air and eliminate the possibilities of air stratification," says Paul Joyce, senior design manager for G and S Consulting Engineers.

For more information about Dry-O-Tron dehumidifiers from Dectron, Inc., circle 102.

Email
Print
Reprint
Learn RSS

Talkback

We would love your feedback!

Post a comment

» VIEW ALL TALKBACK THREADS

Related Content

Related Content

 

By This Author



SPONSORED LINKS

 
Advertisement
Sponsored Links

More Content

  • Blogs
  • Podcast

Blogs


Sorry, no blogs are active for this topic.

» VIEW ALL BLOGS RSS

Podcast

Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Cooling People, Not Buildings with John Suzukida, PE
Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Listen Now | Download MP3 | Subscribe
» VIEW ALL PODCASTS Subscribe Now to HVAC & Building Automation and never miss an episode
Advertisements





NEWSLETTERS
Plug in and get the latest CSE news, trends and industry updates delivered directly to your inbox!

Green Scene
CSE Codes & Standards
CSE NewsWatch
CSE Fire and Life Safety Solutions
CSE Business of Engineering Management Report
CSE Electrical Solutions
CSE HVAC Solutions
Pure Power
CSE Product Showcase
©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites