A Quick Guide for Adding Sprinklers to Historic Structures

By Craig Redfern, P.E. Rolf Jensen & Associates, Inc., Orlando, Fla. -- Consulting-Specifying Engineer, 10/1/2004

Historic designation, by its name alone, implies, at the least, that a designer is going to approach such a project differently from a typical project. In the state of Florida, historic designation also means the particular facility is protected by local and state historic regulatory agencies from requirements of building and zoning rules that may alter its appearance. Adding sprinklers, clearly, will alter appearances. But such structures still require fire-protection and life-safety systems to meet the intent of state and local statutes. For example, Florida requires automatic sprinklers in all non-historic hotels three stories and higher. Here are a few factors to consider when trying to achieve the right balance between preservation and safety:

  1. Develop realistic fire scenarios, defined in terms of fire size and heat release rate and based upon the combustible loading available.
  2. Determine the rate of smoke mass production and associated smoke layer height with respect to time for each fire scenario.
  3. Determine the anticipated occupant loads based upon floor areas and occupant load factors from NFPA 101.
  4. Evaluate egress times based upon the calculated occupant load and proposed egress paths, including appropriate safety factors.
  5. Compare the smoke layer heights with egress times for each scenario.
  • As a way to determine the nature of an existing facility, a timed egress and smoke production analysis allows engineers to evaluate the level of life safety provided in these selected areas of an existing building. One way to do so is to compare calculated egress times to smoke layer heights for specific fire sizes.

    Quantification of anticipated smoke production rates and associated smoke layer heights can be accomplished by conducting an analysis in accordance with established principles of engineering and NFPA 92B.

    The amount of smoke produced for each fire scenario can be determined by the room configuration. The general steps include:

    1. Calculation of the mass flow rate at incremental time steps.
    2. Conversion of the mass flow rate to a volumetric flow rate during each time step.
    3. Calculation of the cumulative sum of the volumetric flow rates determined in Step 2 for all time steps. This yields the total volume of smoke within the compartment at a given time.
    4. Calculation of the layer height from the total volume of smoke based upon the area and height of the ceiling.
  • Finally, consider time of egress. The exit analysis provided by Dr. John Fruin in his "Pedestrian Planning and Design" and several articles by Jake Pauls of the National Research Council of Canada serve as excellent resources. A description of the analysis process is given in Chapter 3–13 of the SFPE Handbook of Fire Protection Engineering (Second Edition - 1995).

    Editor's note: For an in-depth look how this methodology was applied at an historic 19th century hotel, visit the Fire, Life Safety and Security community at www.csemag.com.

  •  

    Sprinkler considerations

    • Develop realistic fire scenarios
    • Determine smoke mass production
    • Determine occupant loads
    • Evaluate egress times
    • Compare egress time to smoke layer height
  • Email
    Print
    Reprint
    Learn RSS

    Talkback

    We would love your feedback!

    Post a comment

    » VIEW ALL TALKBACK THREADS

    Related Content

    Related Content

     

    By This Author

    There are no other articles written by this author.



    SPONSORED LINKS

     
    Advertisement
    Sponsored Links

    More Content

    • Blogs

    Blogs

    • Michael Ivanovich
      Give and Take

      June 19, 2008
      After the flood: mold. Learning from Katrina.
      As Iowa’s flood waters recede and recovery ramps up, the race begins to minimize problems with...
      More
    • Michael Ivanovich
      Give and Take

      February 12, 2008
      Reviving the mentor mentality
      Terry Brennan came into the Solar 101 classroom at Utica, N.Y-based Mohawk Valley Community College,...
      More
    • » VIEW ALL BLOGS RSS
    Advertisements





    NEWSLETTERS
    Plug in and get the latest CSE news, trends and industry updates delivered directly to your inbox!

    Green Scene
    CSE Codes & Standards
    CSE NewsWatch
    CSE Fire and Life Safety Solutions
    CSE Business of Engineering Management Report
    CSE Electrical Solutions
    CSE HVAC Solutions
    Pure Power
    CSE Product Showcase
    ©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
    Use of this Web site is subject to its Terms of Use | Privacy Policy
    Please visit these other Reed Business sites