Understanding an Anomaly - Part 3 - A Hypothesis
August 16, 2007

Performing an average daily energy consumption analysis for the lab facility I have been discussing in the past several posts resulted in the following for pattern for gas consumption. 

The lack of gas consumption prior to February of 2006 along with the change in the electric consumption profile after that point in time clearly indicates when the new gas fired heating equipment came on line and the existing electrically driven heating equipment was decommissioned and shut down.

To check the correlation of energy consumption with climate, I decided to plot the average heating and cooling degree days for the lab location on the graphs. Weather data of this type for a specific location and date range can usually be found on line at the National Climate Data Center for a small fee. More general statistics - for instance average heating degree days for a specific location - can often be found on line at no cost from one of the regional climate centers

Heating and cooling degree days generally indicate the need to heat or cool to maintain comfort conditions in a given climate. But, contrasting energy consumption for a complex building like a lab with degree-day data must be done with a "grain of salt" as the saying goes. For one thing, the degree day calculations assume a balance point where the internal gains exactly equal the losses and no heating or cooling is required (typically, 65°F is assumed, but other base temperatures are also used). For a building that is well insulated and/or with significant internal gains, this may be a bad assumption. In addition, degree days do not directly take the need to humidify or dehumidify into account, so they can be misleading if they are used to calculate energy consumption for cooling or heating. None-the-less, they are a good indicator for the need to heat or cool and can be useful for deciding if consumption patterns are climate driven or are driven by something else.

For the facility that I have been discussing, the gas consumption tends to follow the shape of the heating degree day data (as did the electrical consumption when electricity was the source for heat). In addition, 30% of the peak consumption seems to be related to base load, based on the consumption in the summer months,. A pattern like this often be an indicator of simultaneous heating and cooling. But, at the Oregon coast, night time temperatures can dip into the 50's even in the summer (its realy nice, you should come visit - stay in Neskowin) and thus, there can be a need for some heat, even in the summer, especially for lab systems with high outdoor air flow requirements. Here is what the climate looked like in 2006 based on local hourly weather information which can be obtained from the National Climate Data Center for a small fee .  Each spike is one day.

All of the preceeding doesn't mean that there is not simultaneous heating and cooling going on. Given that the facility is a lab with minimum flow rates fixed by air change requirements and discharge temperatures set by dehumidification requirements, there is probably a reheat load.

Complimenting these consumption based observations is a field observation I made while I was on site on a mild day. Specifically, I notice that a boiler would cycle on and fire for 5-10 minutes and then cycle off for 2-3 minutes and then repeat the cycle. If the cycling can be minimized via set point optimization or some other strategy, the potential exists to improve efficiency by eliminating the losses that occur during the boiler's pre and post firing purge cycles. Thus, my somewhat casual field observation complimented by my knowledge of the general nature of laboratory facilities, the climate at the Oregon coast, and the average daily gas consumption pattern at the facility indicate that there is probably some potential for reducing the baseline consumption.  But, they also say that I probably can't eliminate it.

In contrast, the current electrical consumption pattern has little or no correlation to the climate data. 

While the need to cool in the mild Oregon coastal climate is minimal, there are still days with temperatures in the 80's and even the 90's°F (very nice if you are out on the beach, especially with a sort of sweet white wine) in the peak summer months. Yet, these extremes seem to have little impact on the energy consumption pattern at the facility, even though it the HVAC systems there handle significant quantities of outdoor air. Discussions with the operating staff revealed that in fact, the chilled water system does not operate that frequently and that outdoor air can be used to provide the necessary cooling much of the time. To me, this said that while there may be opportunities to optimize the cooling equipment, they probably should not be my first focus. Stated another way, if I could magically keep the facility comfortable with out ever operating the chilled water system, I probably would not have much effect on the over-all consumption pattern since the chilled water system simply doesn't run that much. As a result, I will likely focus my attention on optimizing things like schedules, looking for throttled valves and dampers, and optimizing flow rates and set points.

Hopefully, this discussion has helped you understand that taking a look at energy consumption patterns via benchmarks and average daily consumption analysis, when combined with other indicators like operator interviews and field observations, can help focus your retrocommissioning and optimization efforts. In the next post, we'll look at how this analysis also helped me understand why site energy consumption went up when common wisdom said it should have gone down when the electric heating equipment was replaced with gas fired equipment.


Posted by David Sellers on August 16, 2007 | Comments (0)



POST A COMMENT
Display Name or Registered Users Login Here.
Please restrict submissions to less than 7,000 characters (including any HTML formatting).

Before submitting this form, please type the characters displayed above:


Advertisement

Advertisements





©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites