LEED-Certified Lighting Pays Off in Other Ways

By Keith Lane, P.E., RCDD/NTS Specialist, LC, LEED AP, Vice President - Engineering, SASCO, Seattle -- Consulting-Specifying Engineer, 5/1/2005

LEED certification can be difficult and expensive to obtain, and therefore requires creative input from all design entities. The electrical engineer can collaborate on several design levels to help the team obtain the intended certification level, particularly when it comes to energy savings from lighting systems.

Lighting controls, as a minimum per local energy code compliance, is required on all LEED projects. In fact, it's a prerequisite. In addition, lighting controls can be a major contributing factor to the Energy and Atmosphere category, Credit 1, Maximizing Energy Performance, and the Indoor Environmental Quality category, Credit 6, Controllability.

The Minimum Energy Performance prerequisite is to meet the minimum level of energy efficiency as specified in ASHRAE/IESNA 90.1 or local energy codes, whichever is more stringent. The basic requirements include the use of occupancy sensors or lighting-control panels to turn lights off during hours of non-use. But another measure that can further improve the baseline energy performance is efficient controls technologies. These can include the use of dimming controls and dimming ballasts; photocells mounted in skylights; dual-technology occupancy sensors; and improved local controls, including those employing the digital addressable lighting interface (DALI) protocol.

In addition, occupancy sensors can be integrated with the mechanical system and the building automation system to change heating and fan control when an area is not occupied.

The combination of the use of sophisticated controls and lamp technology will optimize the points earned in this category. Providing a quality lighting design that implements efficient T8 and T5 lamp technology, as well as the use of light-colored and reflective wall surfaces, can lead to more efficient lighting design.

T5 high-output (HO) fluorescent fixtures can be utilized in parking garages in lieu of traditional metal-halide fixtures as a method to provide more energy-efficient lighting. Fluorescent fixtures provide for increased mean lumens per volt-ampere (LPVA) over traditional metal-halide fixtures. At 40% of fixture life, the T5-HO fluorescent fixture will provide 166% more LPVA. This could provide a tremendous savings over the life of a project, as well as garner LEED points that could be earned with this fixture (see chart below).

Other T5-HO benefits include:
  1. Longer lamp life—20,000 hours compared to 12,000 hours with metal-halides.
  2. Superior and constant color over the life of the fixture. Metal-halide fixtures are notorious for color-shift problems.
  3. A higher color-rendition index (82–85); metal-halide lamps have a CRI of 65–70.
  4. Lower profiles. This can be an important criterion in parking garages with low ceiling clearance, especially in light of the high profile of many SUVs.
  5. Less complex life-safety requirements. Because the time required to re-strike a metal-halide fixture far exceeds the required 10 seconds as specified in NEC 701, Life Safety Systems, a complicated system of quartz-restrike and time-delay relays is often required.
  • The Indoor Environmental Quality category, Credit 6, Controllability of Systems, is intended to improve workers' comfort conditions and productivity. Two credits can be achieved in this section.

    Advanced control

    The first credit, 6.1, requires an average of one lighting-control device for every 200 sq. ft. for all occupied areas within 15 ft. of a perimeter wall. This can be achieved by utilizing independent line-voltage or low-voltage switching or photocell/daylight controls. A higher-end option is to utilize DALI technology. Such a system allows the potential for all occupants to independently control light levels in their work areas.

    Beyond personal comfort, DALI technology can also offer significant energy savings and unequaled control. Luminaires can be controlled separately or in large groups. Because the dimming ballasts have digital addresses, as spaces change, control areas can be reprogrammed. Dimming can be achieved locally or from a central location. Additionally, a central station can monitor energy-use profiles and identify lamp or ballast failure.

    DALI can also be utilized to verify energy savings. This capablity would contribute to the Energy and Atmosphere Credit 5, Measurement and Verification. This credit is intended to promote a design that provides for ongoing accountability and optimization of building-energy and water-consumption performance over time. The requirements to achieve this credit go above and beyond just measuring lighting energy and include: motor loads, variable-frequency drives, chillers, cooling loads, air and water economizers, air distribution, boilers, building processes, indoor water risers and outdoor irrigation systems. Be aware, however, that DALI-generated lighting-energy verification would have to be integrated into the complete BAS.

    Be warned that DALI is also not a panacea. It has not been widely used to date, and there can be difficulties matching components into a cohesive system. Commissioning issues have also restricted its use.

    Other point possibilities

    Another indoor environmental quality credit, 6.2, can be achieved by providing one lighting control per occupant for half of the regularly occupied non-perimeter areas. The same design approach utilized for credit 6.1 also work here.

    Away from the LEED process itself, designing lighting systems to this standard offers additional advantages, one of which is capitalizing on energy incentives sometimes offered by electric utilities. For example, power utilities in the Seattle area offer incentives for lighting systems based on the total kilowatt-hour savings accrued above the energy-code requirements. These savings are calculated over the first year that the building is occupied.

    LEED's renewable energy credit requires that at least 5% of a building's total energy consumption is through the use of on-site renewable energy systems. Technologies required to achieve this credit include solar, wind, geothermal, low-impact hydro, biomass and biogas. If the building gets 10% of its total energy requirements from renewable energy, an additional point is earned. At 20%, a third point is earned.

    Light pollution

    Finally, an area where electrical engineers can help in the LEED process is curtailing light pollution. The intent of LEED 2.1 Credit 8, Light Pollution Reduction, is to eliminate light trespass from the building and the site, improve night-sky access and reduce development impact on nocturnal environments. The designer must first provide lower light levels than those recommended by the IESNA (Illuminating Engineering Society of North America).

    When it comes to reducing light trespass, all exterior light fixtures with more than 1,000 lumens must be shielded, and all fixtures with more than 3,500 lumens must meet the full cutoff classification. Full cutoff will allow no lumens at or above the nadir and candela at less than 10% of rated lumens between 80 and 90 degrees. In addition, the maximum candela of all interior lighting must fall within the building. The intent is to keep light inside the building. The maximum candela value of all exterior lighting shall fall within the property. All pole lighting and lighting mounted on the building façade must also have shielding so that no light from the fixture crosses the property line.

    Computer modeling is required to prove that the design meets the requirements as stated above.

    System Initial LUM VA Initial LPVA Mean LUM LLD Mean LPVA
    Base fixture: 175-watt metal-halide 14,400 222 65 9,300 0.65 42
    T5 HO (2) 8,800 119 74 8,272 0.94 70

    Energy-Optimization Performance Scoring Chart
    New Buildings Existing Buildings Points
    15% 5% 1
    20% 10% 2
    25% 15% 3
    30% 20% 4
    35% 25% 5
    40% 30% 6
    45% 35% 7
    50% 40% 8
    55% 45% 9
    60% 50% 10

  • Email
    Print
    Reprint
    Learn RSS

    Talkback

    We would love your feedback!

    Post a comment

    » VIEW ALL TALKBACK THREADS

    Related Content

    Related Content

     

    By This Author



    SPONSORED LINKS

     
    Advertisement
    Sponsored Links

    More Content

    • Blogs
    • Podcast

    Blogs

    • Michael Ivanovich
      Give and Take

      June 12, 2008
      Useful Green Building Data and Reports
      There have been some good reports released this year on green buildings. Some folks haven't year hea...
      More
    • Michael Ivanovich
      Give and Take

      June 10, 2008
      When the green fad fades
      A few years ago, I was moderating a panel discussion on green buildings at an ASHRAE meeting of the ...
      More
    • » VIEW ALL BLOGS RSS

    Podcast

    Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
    Cooling People, Not Buildings with John Suzukida, PE
    Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
    Listen Now | Download MP3 | Subscribe
    » VIEW ALL PODCASTS Subscribe Now to HVAC & Building Automation and never miss an episode
    Advertisements





    NEWSLETTERS
    Plug in and get the latest CSE news, trends and industry updates delivered directly to your inbox!

    Green Scene
    CSE Codes & Standards
    CSE NewsWatch
    CSE Fire and Life Safety Solutions
    CSE Business of Engineering Management Report
    CSE Electrical Solutions
    CSE HVAC Solutions
    Pure Power
    CSE Product Showcase
    ©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
    Use of this Web site is subject to its Terms of Use | Privacy Policy
    Please visit these other Reed Business sites