You Have the Power! (over Ethernet)

By James Donovan, Director of Global Solutions Management, SYSTIMAX Solutions -- Consulting-Specifying Engineer, 4/1/2005

Power over Ethernet continues to grow more popular, and many companies have already implemented PoE solutions. So what exactly should consultants know about this new technology?

PoE allows the transmission of electrical power over the same Ethernet infrastructure used for data transmission. It extends the capability of the Ethernet infrastructure and delivers power over high-quality category 5e/6 data cables, thereby eliminating the need for extraneous power adaptors, power cords and AC outlets.

Applications

The PoE standard, formally known as IEEE 802.3af, was ratified in June 2003. Prior to the adoption of this global standard, most PoE solutions were mutually incompatible proprietary standards. With the new standard in place, a wide array of PoE devices could be developed with some assurance of interoperability.

A variety of interoperable devices have already been introduced. These include Voice over IP (VoIP) phones, wireless local area network (WLAN) access points and security network cameras. The IEEE 802.3af project was driven by the proliferation of low-power devices that need to be connected to local area networks (LANs). Providing power to these network endpoint devices, in addition to the network connection, results in a cost-effective network infrastructure deployment.

Two options

The PoE architecture consists of two elements: the powered device (PD) and power-sourcing equipment (PSE). Two approaches have been adopted to supply power to a link via a PSE. One approach, which supplies power over the signal pairs (end-span), is intended for use by network equipment vendors. Another option is mid-span power insertion over the spare pairs (10BASE-T and 100BASE-TX networks) designed to support the installed base. Initially, the mid-span approach is a lower-cost solution for legacy networks since it will not require the replacement of the network equipment.

Why PoE?

From a financial perspective, PoE holds the allure of cost savings by eliminating the need for installation of electrical outlets by certified electricians. PoE also provides IT managers with the flexibility to deploy networked devices in optimal locations. WLAN access points can be placed behind ceiling tiles, and security cameras can be placed to provide greater coverage without concern for the AC outlet tether. In addition, network management enables IT managers to monitor and manage powered devices remotely.

Providers of PoE also argue that they offer a more reliable power supply to networked devices, with PDs that are less susceptible to power surges, theft, interruption and disconnection.

And as a standards-based solution, PoE offers vendor-independent interoperability as well as backward compatibility with legacy Ethernet infrastructure. An added benefit of the international standard is that devices do not need separate cords and adapters for different countries.

A growing trend

Though PoE-enabled ports today probably make up only a small fraction of the installed port base for Ethernet LAN switches, in the near term, the use of PoE-powered devices will experience rapid growth as IT managers look to add PoE capabilities to their networks.

 

Potential PoE LAN Devices

  • Internet protocol (IP) telephony
  • Web cameras
  • Wireless access points
  • Industrial automation
  • Security access control and monitoring systems
  • Point-of-sale terminals
  • Lighting control
  • Gaming and entertainment equipment
  • Building management
Email
Print
Reprint
Learn RSS

Talkback

We would love your feedback!

Post a comment

» VIEW ALL TALKBACK THREADS

Related Content

Related Content

 

By This Author

There are no other articles written by this author.



SPONSORED LINKS

 
Advertisement
Sponsored Links

More Content

  • Blogs
  • Podcast

Blogs

  • Michael Ivanovich
    Give and Take

    March 25, 2008
    Wired on Engineering Education
    Scott Siddens, senior editor, sent me an email yesterday that linked to an article on engineering ed...
    More
  • Michael Ivanovich
    Give and Take

    February 12, 2008
    Reviving the mentor mentality
    Terry Brennan came into the Solar 101 classroom at Utica, N.Y-based Mohawk Valley Community College,...
    More
  • » VIEW ALL BLOGS RSS

Podcast

Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Cooling People, Not Buildings with John Suzukida, PE
Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Listen Now | Download MP3 | Subscribe
» VIEW ALL PODCASTS Subscribe Now to HVAC & Building Automation and never miss an episode
Advertisements





NEWSLETTERS
Plug in and get the latest CSE news, trends and industry updates delivered directly to your inbox!

Green Scene
CSE Codes & Standards
CSE NewsWatch
CSE Fire and Life Safety Solutions
CSE Business of Engineering Management Report
CSE Electrical Solutions
CSE HVAC Solutions
Pure Power
CSE Product Showcase
©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites