Electromagnetic compatibility (EMC) is the ability of electrical and electronic equipment to operate in its installation environment while neither causing nor experiencing electromagnetic interference (EMI).
EMI is any interference with normal equipment operation caused by abnormal energy entering the equipment either by conduction though wiring connections or by radiated wave reception. Radiated EMI is also called radio frequency interference (RFI). Conducted EMI is also called high-frequency line noise.
Codes and standards
In the United States, there are no codes and standards that specifically and completely cover electromagnetic compatibility of adjustable frequency drives (AFDs). Part 15 of the Federal Communications Commission (FCC) rules and regulations covers unlicensed equipment that emits radio frequency energy. Part 15 would apply to any AFD as an “incidental radiator.” The operation of any equipment covered by Part 15 is subject to the general conditions of operation listed under paragraph 15.5. The essential requirements of 15.5 are that the equipment must not interfere with any licensed broadcast, navigation or safety services and must accept any interference caused by other equipment. Under Part 15.13, the manufacturer of an incidental radiator “shall employ good engineering practices to minimize the risk of harmful interference.”
Microprocessor-controlled AFDs are also covered by FCC Part 15 as “digital devices.” As commercial or industrial equipment, AFDs are “exempted devices subject only to the general conditions of operation in 15.5 [described above].” However, the FCC strongly recommends that “the manufacturer of an exempted device endeavors to have the device meet the specific technical standards [of Part 15].”
Part 15 lists limits for radio frequency voltage conducted to the public utility power lines by digital devices. The range of frequencies covered is 0.15 to 30 MHz. Part 15 also lists limits for the field strength of radiated emissions from digital devices. The range of frequencies covered is 30 MHz and above. At frequencies lower than the radio frequencies regulated by the FCC, voltages conducted to the power lines would be considered to be harmonic distortion voltages. IEEE Standard 519 covers harmonic distortion issues.
(FCC information and documents are available at https://www.fcc.gov/ as are links to the U.S. Government Printing Office website.)
Evaluating a drive as an FCC 15 device
A drive’s microprocessor is not likely to be a significant source of EMI. The most significant potential source of EMI and RFI in a drive is the power switching circuitry. This potential is largely unrelated to the design of the microprocessor or other type of control circuitry. EMI is generated in a drive by switching the output terminals back and forth between the positive and negative sides of the DC bus to synthesize an AC output waveform. Each time the output transistor switches operate, the terminal voltage jumps (in a 480-volt drive) from 650 volts of one polarity to 650 volts of the opposite polarity. This nearly instantaneous voltage change has the potential to generate a significant amount of radio frequency energy.
Evaluating the drive as a microprocessor controlled “digital device” does not correctly target the most significant source of EMI.
Requiring a drive to meet FCC requirements
Since the applicable requirements are not very specific or restrictive, almost any drive could be said to meet the requirements of Part 15 without actually providing a significant level of electromagnetic filtration.
A drive could be required to meet the conducted and radiated emission limits listed in Part 15 for a Class A or Class B digital device, but Part 15 does not contain or specify a testing procedure that is designed for use with drives. Without specifying a suitable testing procedure, any declaration that a drive meets the specified limits might be suspect.
The conducted emission limits listed in Part 15 were revised in 2002 to “harmonize our domestic requirements with the international standards developed by the International Electrotechnical Commission (IEC), International Special Committee on Radio Interference (CISPR).” (See FCC 02-157). The CISPR 11 standard provides a suitable test procedure for testing drives to verify conformance with these limits.
The radiated emission limits specified by CISPR 22 are lower than the limits listed in Part 15. Accordingly, in 2003, Part 15 was revised to include 15.109(g):
“As an alternative to the radiated emission limits shown in paragraphs (a) and (b) of this section, digital devices may be shown to comply with ? (CISPR) Pub. 22 (1997)?” (See FCC DA 03-3848.)
CISPR 22 covers digital devices, while CISPR 11 covers industrial scientific and medical equipment. The U.S. Food and Drug Administration encourages manufacturers of electromedical equipment to use CISPR 11.
EU Council directives
In the European Economic Community, the EU Council Directives set standards for various products. Many of these standards are derived from standards written by the International Electrotechnical Commission (IEC). The EMC Product Standard for Power Drive Systems, EN 61800-3 (or IEC 61800-3) is used as the main standard for adjustable speed drives. This standard contains test procedures that are specifically suitable for drives, and the standard is quite comprehensive. It covers both the drive’s electromagnetic emissions and its immunity from received emissions.
IEC 61800-3 Defines two Installation Environments:
“The first environment includes domestic premises. It also includes establishments directly connected without intermediate transformer to a low-voltage power supply network which supplies buildings used for domestic purposes.”
“The second environment includes all establishments other than those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes.”
IEC 61800-3 Defines Sale or Distribution to two levels of customer competence:
“Unrestricted distribution is a mode of sales distribution in which the supply of equipment is not dependent on the EMC competence of the customer or user for the application of drives.”
“Restricted distribution is a mode of sales distribution in which the manufacturer restricts the supply of equipment to suppliers, customers or users who separately or jointly have technical competence in the EMC requirements of the application of drives.”
The installer must install the drive in conformance with the instructions provided in the installation manual.
For more information about adjustable-frequency drives from ABB that comply with these requirements, click here .