Prescription for hospital, health care HVAC success

Hospital and health care facility projects are especially important due to their sensitive nature. The HVAC system—especially indoor air quality—must have reliable design.

11/26/2013


Michael Chow, PE, CxA, LEED AP BD+C, Member/Owner, Metro CD Engineering LLC, Powell, Ohio. Courtesy: Metro CD EngineeringGeorge Isherwood, PE, Vice President, Peter Basso Associates, Troy, Mich. Courtesy: Peter Basso AssociatesMichael Lentz, Associate, RMF Engineering, Baltimore. Courtesy: RMF Engineering

Participants

Michael Chow, PE, CxA, LEED AP BD+C, Member/Owner, Metro CD Engineering LLC, Powell, Ohio

George Isherwood, PE, Vice President, Peter Basso Associates, Troy, Mich.

Michael Lentz, Associate, RMF Engineering, Baltimore


CSE: What unique requirements do hospitals and health care facilities’ HVAC systems have that you wouldn’t encounter on other structures?

Isherwood: Equipment redundancy is more common in health care facilities than in other structures. This is due to the failure events that may occur and endanger patients if redundant systems are not properly designed, installed, and commissioned.

Lentz: Redundancy and reliability are the largest requirements that I see. Most health care facilities require some means of redundancy in their HVAC systems so they can still adequately serve patient and critical spaces during an equipment malfunction or failure. The amount of redundancy is always something that has to be weighed and measured against the project budget and the type of program space that is being built. For example, 100% redundancy for the HVAC system is more suitable for operating rooms and patient spaces than material holding or administrative offices. How you achieve this type of redundancy is also something that is unique to each facility. Is the redundancy a standby air handling unit, a standby supply fan, a fan wall assembly, or a manifold system that can withstand the loss of partial supply air?

CSE: What HVAC techniques or tools have you used to reduce the possibility of hospital-acquired infections (HAIs)?

Lentz: Strict pressurization requirements between different program areas within the hospital, and filtration and separation of different program areas within the hospital. For example, applying 100% exhaust to the emergency department waiting rooms. Any airborne infection isolation room exhaust is treated with high-efficiency particulate air (HEPA) filtration. All critical spaces, such as operating rooms, recovery areas, and sterile processing departments, are equipped with return or exhaust air terminal units in order to maintain correct pressurization within the program area, even if there is a loss of supply air to the space.



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
May 2018
40 Under 40 winners, fire and life safety, performance-based designs, and more
April 2018
VRFs, lighting controls, BIM coordination, and more
March 2018
Sizing water pipes, ASHRAE 90.1, recovering waste heat, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me