Your questions answered: Pathogen Control by Design

Pathogen control problems in plumbing systems should be carefully guarded against. Here is additional information to supplement the webcast on “Pathogen Control by Design.”

11/19/2015


Pathogen control in plumbing systems should be carefully guarded against. Here is additional information to supplement the webcast on “Pathogen Control by Design.” Courtesy: Legionella Risk Management Inc.Several questions were asked by the audience at the Nov. 10, 2015, webcast on "Pathogen Control by Design." Tim Keane, Legionella Risk Management Inc., answers some of the most relevant ones here.

Question: With elevated temperatures on supply and return piping, what is the maximum velocity that should be allowed?

Tim Keane: Velocity of 3 to 5 fps is very good.

Question: Regarding slide 44, is it the intent to circulate cold water also? Hot water to a fixture group is usually dead ended, so is it the intent to circulate all dead ends?

Keane: Hot water only should be recirculated. Slide 44 is not recirculation; it is series flow from shower to sink so every time the sink is used, water is flushed through the shower to turn over the potentially stagnant water in the shower drop let.

Question: Is ASHRAE 188-2015: Legionellosis: Risk Management for Building Water Systems currently referenced by any codes?

Keane: Sentences of Standard 188 are now in NYC and NYS codes. Typically it takes a year to several years for a standard to get adopted

Question: How does heat trace work to maintain temperature in the hot water system? Or is it better to keep the water moving to not allow the growth of the Legionella?

Keane: There is no study to show impact of heat tracing. Heat tracing would be added when stagnant flow conditions result in temperature reduction to levels of concern. My guess is heat tracing in areas of prolonged little to no flow will typically not be beneficial and may worsen the problem.

Question: Does water softening and/or a scale treatment (i.e. scale safe) increase chances of bacterial growth?

Keane: Phosphates are good nutrients for bacteria.

Question: Can Legionella form in kiddie daycare water park pads in south Texas if not treated with chlorine or other filter system?

Keane: Absolutely.

Question: If we have Legionella in a cooling tower, how does it get to our main domestic system?

Keane: It doesn't get from a cooling tower into a pressurized potable water system. Legionella is frequently in city water, usually at undetectable levels.



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me