PV system fundamentals

Photovoltaic (PV) systems are one of the best options for on-site power generation. Commercial buildings must generate power as we move forward with the AIA 2030 challenge, net zero energy, and other energy efficiency programs

Learning objectives:

  • Outline the basic information about solar photovoltaic (PV) systems.
  • Analyze the best application, location, and use for PV systems.
  • Calculate PV panel size and electrical requirements.

The latest solar photovoltaic (PV) market report from Greentech Media and the Solar Energy Industries Association (SEIA) forecasts another record year for the U.S. PV market in 2015, with an estimated 27% growth over 2014. Moreover, growth should accelerate beyond 2015 as the 30% federal Solar Investment Tax Credit (ITC) is set to expire Dec. 31, 2016. It’s anticipated the expiration of the ITC will send the market into a frenzy as consumers rush to take advantage of the benefit. As costs continue to decrease and consumers continue to yearn for PV, the demand will only increase. The engineering community must quickly get up to speed on how to design and specify PV systems.

The sun produces essentially an infinite amount of energy. The Earth receives approximately 170 million GW of power from the sun, which is millions of times greater than global power demand. Solar irradiance is the power of solar radiation per unit of area, measured in Watts per square meter (W/m2). The Earth’s solar irradiance constant is approximately 1,366 W/m2 (nominally 1,000 W/m2). Solar irradiation, or solar energy, is the solar power accumulated over time. The unit of measure is Watt-hours per square meter (Wh/m2). The greater the solar irradiance for a given location, the more energy is generated.

The preceding information is necessary for interpreting insolation, or solar irradiation, maps. Insolation maps are used to rate the solar energy resources of a location. The National Renewable Energy Laboratory (NREL) produces insolation maps for reference.

It’s important to also understand the sun path or solar window for a given location, which depends on geographical location and time of year. The two angles most important to PV designers are the azimuth angle (relationship to due south) and altitude angle (the sun elevation angle), as they directly impact the design and energy yield. A PV module (i.e., panel) receives the maximum amount of energy when the direct component of solar radiation is exactly perpendicular to the module surface. Most locations in the U.S. will have a steeper tilt in the winter months to align with the lower winter sun and a flatter tilt in the summer for the high summer sun. The University of Oregon has an excellent program for generating sun path charts to analyze sun angles throughout the year for various locations. Because PV modules are generally fixed, the designer is required to make a compromise between summer and winter energy production. The angle is typically chosen to maximize annual energy generation with an angle within 15 deg of the latitude resulting in the best yield.

PV cells and modules

Photovoltaics is a solar technology that uses the electrical properties of various types of semiconductor materials to directly convert sunlight into electric power. The resulting electricity is direct current (non-sinusoidal). The basic physical process is known as the PV effect. When high-energy photons of sunlight strike a semiconductor material and are absorbed, the energy is transferred to the electrons in the semiconductor material. The extra energy excites the electrons to the point where they break free from their associated atom. The free electrons are directed through an external circuit to a load where the flow of electrons (i.e., current) can do useful work. This process occurs continuously as the semiconductor material is exposed to daylight.

Photovoltaic cells are the basic building blocks of a PV module and are typically made of crystalline silicon material. Many other materials are available for PV cell production, but crystalline silicon dominates the power generation market. Crystalline silicon cells are manufactured through a variety of techniques. The basic steps in the manufacturing process are silicon purification, crystal ingot formation, wafer production, doping, application of electrical contacts, and cell encapsulation.

Monocrystalline silicon cells are made from a single silicon crystal resulting in high efficiency (16% to 21%). Polycrystalline silicon cells are composed of many silicon crystals and have a lower efficiency (11% to 15%). The individual PV cells are combined in series and parallel connections to form modules, often referred to as panels. Series connections are made to build voltage. Parallel connections are made to build current. The power output of the module is voltage multiplied by the current (P = V x I). Standard modules are either 60 or 72 cells and current modules are rated at 260 W to 300 W. Similar to PV cells, modules are connected in series and parallel to increase voltage and current. A group of modules is called an array (see Figure 1).

A PV system is defined as all the components required to allow the system to produce useful power. This includes modules, wiring, conduit, combiner boxes, overcurrent protective devices (e.g., fuses and circuit breakers), disconnect switches, inverter(s), meters, mounting hardware, etc. PV systems can be configured in various ways such as grid-tied (utility interactive) or off grid (stand-alone) (see Figures 2 and 3).

Grid-tied is the most common PV system configuration because it’s the easiest to design and less expensive when compared with a stand-alone system, which relies on batteries. The application of the system will determine the system configuration. Applications for PV systems include space exploration, vehicles, electronics, remote lighting, signage, telecommunications, water pumping, and baseload power. With respect to size classification, residential systems are rated less than 20 kW, commercial systems are 20 kW to 1 MW, and utility size systems are larger than 1 MW.

Site survey and planning

The first stages of a PV project involve researching the location and surveying the site. It is crucial to know the climatic conditions, most notably the high and low temperatures and solar insolation. The Solar America Board of Codes and Standards has a reliable reference map for obtaining temperature data. Temperature is perhaps the most important factor when sizing the array and balance of system (BOS) components. This is due to the fact that the voltage and current produced by the cells are dependent on the ambient temperature and insolation at the site. That is, the voltage of the module is higher in colder temperatures and the current increases with higher insolation values (see Figure 4).

It’s also important to consider factors such as wind speed, corrosion, severe weather, lightning strikes, seismic activity, and the potential for vandalism and theft. Local building codes and city ordinances, permitting, inspection, interconnection requirements, and financial incentives must also be investigated prior to design. These factors may influence how the system is designed and installed.

The location should be surveyed prior to design to evaluate shading concerns and existing roof conditions. Shading is a huge concern. Even a small amount of shade during the day could have a detrimental effect on the system performance. The age and condition of the roof may warrant a total roof replacement, as the life of the PV system is 30 yrs or more.

Following the initial site survey, array sizing is the next task to consider. At this point, the first question to ask is, “What am I designing for?” The answer will influence how the system is designed. For example, are you trying to maximize annual energy yield? Maximize the kilowatt rating? Are you working within a limited footprint? Are you working with a fixed budget? You won’t be able to design an array layout until you know the objectives and constraints.

Most PV modules are manufactured to a standard dimension around 66×38 in. By using software such as Autodesk AutoCAD or Revit, you can quickly create different layouts using portrait or landscape module orientation, different tilt angles, etc. This is a trial-and-error exercise where the goal is to determine the most efficient layout while satisfying your constraints and objectives. There will be several iterations before you arrive at a preferred layout. You must also calculate the row-spacing distance to avoid inter-row shading. You can use trigonometry to hand-calculate the spacing, or use an online calculator. The approximate rule of thumb for spacing between rows should be 2½ to 3 times the height of the tilted module.

Your final PV array layout provides the total quantity of modules, which will give the dc power rating for the system. The rule of thumb for array size based on area is 8 to 10 W/sq ft. A useful tool for estimating annual energy production is the PVWatts calculator from NREL. The PVWatts calculator allows you to quickly estimate your production based on location, tilt angle, and other factors. More sophisticated designers can use a program called PVsyst for PV-system modeling.

Calculations for PV systems

The basic grid-tied system consists of a PV array, an inverter, the loads, and the electric utility. Calculations are required to properly connect the modules, select the inverter, and size the circuits. The first step is connecting the modules to build an array. Modules connected in series are referred to as series strings. NFPA 70: National Electrical Code (NEC) refers to a series string as a PV source circuit.

The quantity of modules that can be connected in a series string is limited by the system operating voltage, typically 600 V. Larger systems might be higher at 1,000 V. According to NEC Article 690.7 and its related table, the maximum PV source circuit voltage shall be calculated as the sum of the rated open-circuit voltage of the series-connected modules corrected for the lowest expected ambient temperature. The open-circuit voltage (VOC) is the maximum voltage generated by a PV module and can be obtained from the PV module data sheet. If a data sheet is not available or there are multiple modules being considered, then the NEC provides a generic table of correction factors for crystalline silicon modules. Refer to NEC table 690.7, and see the sidebar titled “Calculation examples.”  If string sizing doesn’t seem like fun, then there are online string-sizing programs to help.

Once you have the string size, then you can move on to the combiner box. A combiner simply is a box that “combines” multiple series strings. That is, there are multiple inputs and a single output. Think of it as the opposite of a panelboard. The system may or may not need a combiner box depending on the number of strings and the capabilities of the inverter.

The PV source circuit’s maximum current is given as the module short-circuit current (ISC). This is the current generated by the module when exposed to sunlight with the output terminals shorted. The short-circuit current is used when parallel-connecting the series strings. The PV output-circuit current is the sum of the PV source circuit currents.

NEC Article 690.8 has specific requirements regarding the calculation of the maximum circuit currents, ampacity, and overcurrent protective device (OCPD) ratings. This article requires the PV source circuit current be multiplied by 125% to account for the fact that PV modules can produce higher currents under high-irradiance conditions (i.e., current increases with more sunlight). Therefore, the PV output-circuit current is the sum of the source-circuit currents including the 125% factor.

Another 125% factor must be applied when calculating wire ampacity and  OCPD ratings to account for continuous equipment operation (more than 3 hrs). Please note the string-sizing program already mentioned can also perform the task of inverter selection based on your array-power rating and string size.

The next step is inverter selection. The basic function of the inverter is to change the dc output of the PV array to ac electricity for use in the building. Modern-day inverters use power electronics to accomplish this. Inverters fall into the following three categories: micro, string, and central inverters.

Micro-inverters are small module-level inverters that convert the dc output to ac at each module. When mounted directly to the module, they are referred to as ac modules. The advantage of micro-inverters is they allow greater tolerance for shading, and modules can be mounted at different tilt angles and facing different directions. This helps when you have a roof with different slopes and orientations. String-inverters are suited for small to medium-size PV arrays and combine a small number of series strings together at the inverter without the need for a combiner box. Central-inverters are the largest inverters and are rated for higher kilowatt values. They are made for large commercial and utility-scale projects.

The inverter size should be chosen to be lower than the dc rating of the PV array, about 80% to 100% of the array dc power rating. This “derate” factor accounts for typical system losses. Sizing the inverter equal to or greater than the array dc power rating is simply wasting money. Be sure the inverter’s input current and voltage range is compatible with the voltage and current of the PV array.

At this point, the output of the inverter typically connects back into the building ac system. The most common method is a back-fed circuit breaker within a building panelboard. NEC Article 705.12 states that the sum of the OCPD ratings of the circuits supplying power to a panelboard busbar shall not exceed 120% of the rating of the busbar. The PV circuit breaker also needs to be suitable for back-fed operation (see Figure 5).

Important code requirements

Other notable code requirements are specified in NEC Articles 690.5, 690.11, and 690.12. Article 690.5 states PV arrays shall be provided with ground-fault protection capable of detecting and interrupting a ground fault in the dc current-carrying conductors and components. Article 690.11 requires PV systems to be protected by a dc arc-fault circuit interrupter. Both Articles 690.5 and 690.11 are intended to prevent or mitigate fires associated with ground faults and arcing-type faults occurring in dc circuits. Article 690.12 requires rapid shutdown of PV systems on buildings. The intent of Article 690.12 is to control (shut off) the dc conductors near the array to remove power from inside the building. This is important for firefighters and first responders to ensure power is off when trying to extinguish a fire.  Note there is no way to turn off PV modules. PV modules will stop producing current only when the sunlight is no longer striking the modules.

PV-array mounting

PV arrays can be mounted in many ways including ground-, roof-, and building-integrated. Ground- or roof-mounted arrays have the option to be permanently secured to the ground or roof or self-ballasted. Building-integrated PV systems are those where the array substitutes a building material such as an awning, window(s), roof material, or skylight. Arrays can be fixed, manually adjustable, or sun-tracking. Sun-tracking takes advantage of always self-positioning the array at the optimal sun angle and can be single- or dual-axis. Regardless of the mounting method, the strength and rigidity of the supports and structure must be evaluated for all expected loads (e.g., dead, live, wind, snow, vibration).

Thomas Edison’s vision of using solar power as a viable energy source has come of age with the widespread proliferation of PV technologies. Consumers are demanding it, and the market potential is explosive. Now is the time for engineers to get educated and provide the design services required to implement PV technology.

Calculation examples

Two examples provide insights on how to calculate photovoltaic (PV) modules.

Example 1: Given the NFPA 70: National Electrical Code (NEC) information in NEC table 690.7 and the PV-module data in Table 2, calculate the maximum quantity of module you can connect in series. Assume the system voltage is 600 V and the location is Detroit.

The maximum quantity of modules connected in series without exceeding the 600 V based on the location is 12 modules.The first step is to go to Solar America Board of Codes and Standards and find the lowest ambient temperature to determine the proper correction factor. The extreme minimum is -19 C. Based on NEC table 690.7, the correction factor would be 1.18. The maximum number of modules (NM) connected in series is given below.

Example 2: Given a PV module with the values in Table 1, calculate the PV source circuit and output-circuit currents used to size wire ampacity and overcurrent protective device ratings. Assume your plan layout produced a PV array with 96 modules.

The 96 modules provide 8 strings (assuming 12 modules per string). The maximum PV source circuit current (ISCC) would be equal to the module short-circuit current (9.71 amps) multiplied by 125%. The ampacity used to size PV source circuit conductors would require an additional 125% multiplier.

The ampacity used to size the PV output circuits (IOCC) would be the sum of the ISCC values calculated above.

The PV output-circuit ampacity, combiner-box ampacity, and inverter-current rating would need to be rated for at least 182 amps.


Mike Nowicki is an associate electrical engineer at SmithGroupJJR. He is responsible for developing the overall building electrical systems design, including primary and secondary power distribution, lighting, alternative energy systems, communication, and security systems. Nowicki holds a bachelor’s degree in electrical engineering and a master’s degree in alternative energy technology, both from Wayne State University.