Specifying drop-out ceilings beneath fire sprinklers

Fire protection engineers can specify ceilings beneath fire sprinklers, as identified in NFPA 13.

11/16/2016


Learning objectives

  • Identify the various ways in which fire sprinklers can be suspended below a ceiling
  • Learn about NFPA 13, the standard that identifies fire sprinkler installation
  • Review the benefits, costs, and other issues associated with drop-out ceilings and fire sprinklers.  

Figure 1: This food kiosk, in the atrium of a shopping mall, required a roof to protect food handling areas against contaminants thrown from the upper level. An ordinary roof would block water from sprinklers located at the mall ceiling level. The solutioThe very idea of suspending ceilings beneath automatic fire sprinklers sounds topsy-turvy. Sprinklers, the mind insists, must project into the space they protect so they can release their deluge without interference—even if it means cutting holes in ceiling panels and dropping pipes so sprinklers extend to the underside of the ceiling.

Yet at the same time, many designers yearn to unshackle sprinklers from ceilings. Surely, they intuit, there must be a way to:

  • Simplify coordination of sprinkler and ceiling location
  • Reduce sprinkler and ceiling installation costs
  • Satisfy architectural concerns about the visual impact of sprinklers
  • Get sprinklers out of occupied spaces where they can be damaged or difficult to clean. 

One can, of course, simplify sprinkler and ceiling coordination by eliminating suspended ceilings and leaving the structure exposed. Ironically, this approach may not be the most economical if it adds the cost of painting overhead surfaces, exercising more care in locating the ducts, pipes, conduit, and other exposed-to-view services, and installing sound-absorbing materials to satisfy acoustical criteria. Plus, exposed services provide surfaces that collect dust and grime and may not be permitted in occupancies requiring hygienic conditions.

Another approach is to install sprinklers above a ceiling system with 70% minimum open area as permitted by NFPA 13: Standard for the Installation of Sprinkler Systems, 2016 edition, Paragraph 8.15.14. This still leaves the structure and services significantly exposed and presents many of the same drawbacks as having no ceiling. If the ceiling consists of egg crate, louver, or honeycomb panels, the ceiling can restrict the sideways travel of the sprinkler discharge. Lighting efficiency also is decreased because at least 70% of any light impinging on the ceiling from below is lost into the cavity above, and at least 30% of lumens from above-ceiling lamps are blocked if using a luminous ceiling scheme.

This article explores a third approach—drop-out ceilings. NFPA 13, Paragraph 3.3.9, defines a drop-out ceiling as:

A suspended ceiling system, which is installed below the sprinklers, with listed translucent or opaque panels that are heat-sensitive and fall from their setting when exposed to heat.

Figure 2: The drywall soffits required sprinklers both above and below the soffit. If a drop-out ceiling had been used, the sprinklers beneath the soffit could have been eliminated. Courtesy: CeilumeDrop-out ceiling systems have been in use since the development in the mid-20th century of modern suspended ceiling systems and suitable plastics. Most drop-out ceilings are made from either expanded polystyrene (EPS) foam or are thermoformed ceiling (TFC) panels. The thermal insulation properties of EPS make it useful in cold-storage facilities where they enable wet pipe fire sprinkler systems to be installed above rooms with freezing temperatures. EPS ceilings have many limitations, however, that have discouraged specifiers from considering drop-out ceilings in the past.

TFCs overcome these limitations, justifying a re-examination of drop-out ceilings. They are made from thermoformed vinyl just 0.013- or 0.030-in. thick. When exposed to sufficient heat, the vinyl panels soften, sag, and fall out of a standard metal ceiling grid. This exposes above-ceiling sprinklers to rising heat and allows sprinklers to activate without interference. The panels harden when they reach the relatively cooler floor and do not add meaningfully to the fuel load. 

Cost and construction

Installing drop-out panels beneath sprinklers can be significantly less expensive than using mineral fiber panels with penetrating sprinklers. For example, drop-out ceilings eliminate the need to extend pipes from sprinkler mains to ceiling elevation. It becomes unnecessary to position sprinklers at panel centers; this means the layout of sprinklers can be optimized, shop drawings to coordinate sprinklers and ceiling installation can be eliminated, and less piping is required. Economical sprinklers styles can be used and decorative finishes, trim rings, and escutcheons can be eliminated. Ceiling installers do not have to cut holes for sprinklers. And sprinkler installers do not have to return to the project to adjust sprinkler locations after ceiling installation.

The affordability of any installation depends on the project conditions, products, and performance levels required. Thermoplastic panels, for example, are more affordable than high-performance and decorative mineral fiber panels and competitively priced with ordinary mineral fiber products.

Figure 3: While not required by NFPA standards, installation of a placard with information for firefighters, code authorities, and facility managers is recommended. The placard should be located near fire system valves or conspicuous location. Courtesy: CWhile labor to install panels is similar regardless of material, cutting individual thermoformed panels for perimeter units may cost slightly more than scoring and breaking square-edged mineral fiber tiles and about the same as trimming tegular panels. However, waste will be reduced because thermoformed panels do not break easily during handling, as is common with mineral fiber panels. Thermoformed panels also nest compactly and several panels can be cut simultaneously with aviation snips.

As an example, an independent construction consultant prepared a detailed construction cost estimate comparing thermoformed and mineral-fiber ceiling panels for a 110,000-sq-ft office building in Oklahoma City. He investigated two scenarios and found that the drop-ceiling approach generated savings ranging from 72 cents to $3.29/sq ft, depending on the product selection. The estimate is based on open-shop wages, and savings are likely to be even greater in areas with prevailing wage rates. 


<< First < Previous Page 1 Page 2 Next > Last >>

Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me