Your questions answered: Pathogen Control by Design

Pathogen control problems in plumbing systems should be carefully guarded against. Here is additional information to supplement the webcast on “Pathogen Control by Design.”

11/19/2015


Pathogen control in plumbing systems should be carefully guarded against. Here is additional information to supplement the webcast on “Pathogen Control by Design.” Courtesy: Legionella Risk Management Inc.Several questions were asked by the audience at the Nov. 10, 2015, webcast on "Pathogen Control by Design." Tim Keane, Legionella Risk Management Inc., answers some of the most relevant ones here.

Question: With elevated temperatures on supply and return piping, what is the maximum velocity that should be allowed?

Tim Keane: Velocity of 3 to 5 fps is very good.

Question: Regarding slide 44, is it the intent to circulate cold water also? Hot water to a fixture group is usually dead ended, so is it the intent to circulate all dead ends?

Keane: Hot water only should be recirculated. Slide 44 is not recirculation; it is series flow from shower to sink so every time the sink is used, water is flushed through the shower to turn over the potentially stagnant water in the shower drop let.

Question: Is ASHRAE 188-2015: Legionellosis: Risk Management for Building Water Systems currently referenced by any codes?

Keane: Sentences of Standard 188 are now in NYC and NYS codes. Typically it takes a year to several years for a standard to get adopted

Question: How does heat trace work to maintain temperature in the hot water system? Or is it better to keep the water moving to not allow the growth of the Legionella?

Keane: There is no study to show impact of heat tracing. Heat tracing would be added when stagnant flow conditions result in temperature reduction to levels of concern. My guess is heat tracing in areas of prolonged little to no flow will typically not be beneficial and may worsen the problem.

Question: Does water softening and/or a scale treatment (i.e. scale safe) increase chances of bacterial growth?

Keane: Phosphates are good nutrients for bacteria.

Question: Can Legionella form in kiddie daycare water park pads in south Texas if not treated with chlorine or other filter system?

Keane: Absolutely.

Question: If we have Legionella in a cooling tower, how does it get to our main domestic system?

Keane: It doesn't get from a cooling tower into a pressurized potable water system. Legionella is frequently in city water, usually at undetectable levels.



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
November 2018
Emergency power requirements, salary survey results, lighting controls, fire pumps, healthcare facilities, and more
October 2018
Approaches to building engineering, 2018 Commissioning Giants, integrated project delivery, improving construction efficiency, an IPD primer, collaborative projects, NFPA 13 sprinkler systems.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me