Watching the Lights: A Reliable PQ Indicator

The flicker chart below shows one measure of how power disturbances can affect power users. At any point above the orange line, light flicker will be noticeable, while above the purple line people will begin to become irritated by the intensity and frequency of the flicker.Flickering of the lights is a definite indication that there are voltage variations in the distribution system.

01/01/2001


The flicker chart below shows one measure of how power disturbances can affect power users. At any point above the orange line, light flicker will be noticeable, while above the purple line people will begin to become irritated by the intensity and frequency of the flicker.

Flickering of the lights is a definite indication that there are voltage variations in the distribution system. While this chart is intended for use with incandescent fixtures, it may be applied to fluorescent fixtures with a suitable scaling factor, as fluorescents are not as sensitive to voltage variance.

The chart is not as accurate for high-intensity-discharge (HID) sources since a dip in the supply voltage does not result in the same reduction in intensity of the lamp output as it does with incandescents. Also, if the voltage dips too much, the HID lamp will completely extinguish-requiring it to restrike-while the incandescent or fluorescent lamps will immediately turn back on.





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
April 2018
VRFs, lighting controls, BIM coordination, and more
March 2018
Sizing water pipes, ASHRAE 90.1, recovering waste heat, and more
January/February 2018
Sizing water pipes, ASHRAE 90.1, recovering waste heat, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me