Warehouse commissioning lighting system

By commissioning the lighting system, this company saved electricity and improved the safety of its high-bay lighting fixtures in this warehouse.

12/11/2014


Figure 3: The Whirlpool Rickenbacker Distribution Center’s 1,000+ lighting fixtures were commissioned to ensure safety and efficiency throughout the warehouse building. Courtesy: Metro CD Engineering LLCThe Whirlpool Rickenbacker Distribution Center is a 1.6-million-sq-ft facility located in Columbus, Ohio. The project achieved LEED v2.2 Certification. The building has more than 1,000 lighting fixtures in the warehouse section alone.

The owner’s project requirements (OPR) stated that the warehouse use high-bay lighting fixtures with integral motion sensors installed to provide an average maintained level of 20 foot-candles at 2.5 ft above the finished floor and 40 foot-candles in the staging bays.

The OPR also stated that storage lighting will have a 2-minute delay on the motion sensors and 20-minute delay on the staging bays.

The commissioning authority was Michael Chow, PE, CxA, LEED AP BD+C, with Metro CD Engineering. The commissioning team verified that the motion sensors were adjusted and functioned in accordance with the OPR and the manufacturer’s installation instructions. A 20% sampling of the motion sensors was done for the functional testing.

Commissioning of the lighting control systems is a key factor in the facility’s success. Having the lights turn on when needed and turn off when not needed is critical to ensuring the distribution center operates safely and does not waste electricity.


Michael Chow is the founder and owner of Metro CD Engineering. He holds a BSEE from Ohio Northern University and is a member of the Consulting-Specifying Engineer editorial advisory board and a 2009 40 Under 40 winner.



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me