Top MEP considerations when designing for elevator systems

Designing multistory buildings requires architectural teams to carefully plan elevator systems that meet current safety standards as well as address the unique needs of the space. This whitepaper will discuss mechanical, electrical, plumbing, and fire protection considerations for designing a safe and efficient elevator system.

07/08/2016


Designing multistory buildings requires architectural teams to carefully plan elevator systems that meet current safety standards as well as address the unique needs of the space. This whitepaper will discuss mechanical, electrical, plumbing, and fire proIn recent years, there has been a growing trend toward architectural projects that focus on building upward instead of sprawling outward. When land is limited, particularly in urban areas, this is the most efficient use of space and resources. In Chicago alone, the number of active high-rise construction sites more than doubled (from 14 to 34) from October 2014 to January 2016.

Designing multistory buildings requires architectural teams to carefully plan elevator systems that meet current safety standards as well as address the unique needs of the space. This whitepaper will discuss mechanical, electrical, plumbing, and fire protection (MEP/FP) considerations for designing a safe and efficient elevator system.

Types of elevators

Hydraulic vs. traction elevators

When designing for an elevator system, it is important to first determine which type of elevator suits the project's needs. Hydraulic and traction elevators have different requirements and specifications, and building height is a major factor in which one is appropriate for a project.

Hydraulic

Pumps that are generally 30 to 40 hp move hydraulic fluid under a piston to raise this type of elevator and then return fluid back into the tank to lower the elevator. Hydraulic elevators are advisable for shorter buildings, up to 5 stories. They also contain flammable liquid and must feature appropriate fire alarm and protection devices.

Traction

Traction elevators, on the other hand, are suspended by tensile cable and balanced by counterweights equal in weight to a half-loaded elevator. They are raised and lowered by moving the cable. Traction elevators are commonly installed in buildings that have more than 5 stories and use motors that are generally 15 to 20 hp.

Traction elevator machinery has traditionally been located in penthouse spaces above the elevator shaft; however, "machine roomless" elevators are now available for buildings up to 150 ft tall. This centralizes all machinery within the shaft, saving the client the cost of building a dedicated penthouse space.

Designing multistory buildings requires architectural teams to carefully plan elevator systems that meet current safety standards as well as address the unique needs of the space. This whitepaper will discuss mechanical, electrical, plumbing, and fire proSmoke control and pressurization

Modern buildings are designed to contain a fire to the location where it starts, and floor plates generally are rated to prevent movement of smoke and growth of a fire. For this reason, care must be taken with shafts that penetrate multiple floor levels, because they are susceptible to collecting smoke from a fire or transferring smoke from floor to floor.

Smoke control normally is operated automatically by the fire alarm system, but firefighters need the ability to override the system. Because of this, smoke control is required to be annunciated and manually operated from a firefighter's smoke control panel.

Hoistway ventilation

In the past, hoistway ventilation was the main approach to smoke control. When smoke was detected in an elevator shaft or lobby, vents in the top of the shaft would open to discharge smoke. Hoistway ventilation is becoming less preferable because it can exacerbate problems through stack effect, drawing smoky air from the fire floor through the shaft.

Hoistway pressurization

Pressurization is an alternative smoke control solution, which begins when a building's fire alarm system is activated. It works by positively pressurizing the hoistway and pushing air outward through any opening, avoiding smoke infiltration.

Emergency power

Emergency power is a primary concern in new building design, especially since high-rise buildings are becoming more commonplace, and they are simply not accessible without elevators.


<< First < Previous Page 1 Page 2 Next > Last >>

Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
November 2018
Emergency power requirements, salary survey results, lighting controls, fire pumps, healthcare facilities, and more
October 2018
Approaches to building engineering, 2018 Commissioning Giants, integrated project delivery, improving construction efficiency, an IPD primer, collaborative projects, NFPA 13 sprinkler systems.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me