Top 10 design tips for condensing boiler systems

There are ten design items that should be considered for designing condensing boiler systems.

12/16/2013


In addition to pumping setup, the following top 10 design items should be considered when designing condensing boiler systems.

1. Cost impacts: A condensing boiler has a more expensive initial cost than an equally sized noncondensing boiler. To gain the efficiency benefits, the system must be designed for condensing temperatures.

2. Boiler controls: Purchase and install a boiler management system dedicated to control the boilers to optimize the boiler system efficiency. Running more boilers at lower loads provides better efficiency for condensing boilers.

3. Boiler heat exchanger: Understand the heat exchanger style selected and the potential limitations of the heat exchanger selection. It may require mixing valves and extra pumps to allow condensing to occur only where desired.

4. Flue materials and locations: Individual flues are generally required due to the high variability of airflow and the boilers will require fans to remove the products of combustion out of the building. Coordinate flue materials with the manufacturer selected.

5. Drains required: Condensate drains are needed at the base of the flue stack and the heat exchanger with condensate traps. Coordinate plumbing drainage systems required with the plumbing engineer to confirm the drains are compatible with the acidic condensate.

6. Hot water return temperature: The lower the hot water return temperature to the boiler, the better the system efficiency. Design the system for the lowest possible hot water supply temperature but be careful of aggressive hot water reset schedules that assume energy savings. (Many times reset schedules use more energy due to higher flow requirements at lower temperatures.)

7. Minimum boiler flow: Generally, some type of minimal flow is required for the boilers. Provide a minimum flow bypass valve or a few three-way valves in the system design to maintain the minimum flow required by the boiler.

8. Pumping arrangements: Some boiler manufacturers prefer to pump into the boiler, and some prefer to pump away from the boiler. Provide variable primary pumping when possible, which always provides lower initial and operating costs. Make sure to include two-way, two-position control valves at each boiler to prevent flow to a boiler when it is not in use.

9. Larger heating coil requirements: Larger, deeper coils will be required with lower hot water supply temperatures. Pay close attention to pressure drops.

10. Follow the manufacturer’s instructions: Every boiler manufacturer is different, and not following the installation guidelines could void the warranty. Always confirm the design requirements with the specific boiler manufacturer selected.


David Grassl is a mechanical engineer at Ring & DuChateau, a consulting engineering firm based in Milwaukee, and an adjunct professor in the Civil & Architectural Engineering & Construction Management Department at the Milwaukee School of Engineering. He has analyzed and designed multiple heating plants including steam boilers, standard boilers, and heat recovery/condensing boiler systems. 



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
November 2018
Emergency power requirements, salary survey results, lighting controls, fire pumps, healthcare facilities, and more
October 2018
Approaches to building engineering, 2018 Commissioning Giants, integrated project delivery, improving construction efficiency, an IPD primer, collaborative projects, NFPA 13 sprinkler systems.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me