Things to keep in mind when analyzing daylighting in AGi32

Accurate daylight analysis requires using the correct surface designation for exterior, but not interior, surfaces.

06/20/2013


The key to accurate daylight analysis using AGi32 is the assignment of the correct surface type designation to glazing and exterior surfaces. Interior surfaces require no special treatment. Daylighting calculations using AGi32 follow several important assumptions:

  • AGi32 considers the following daylight components: sunlight, skylight, and light reflected from a “virtual” ground plane.
  • Daylight can only be seen by an interior surface (interior of a room or object) after it has passed through a “daylight transition surface.” This is typically daylight transition glass.
  • All exterior surfaces must be classified as “daylight exterior surfaces” to accumulate daylight components.
  • “Daylight transition surfaces” will consider light reflected only from “daylight exterior surfaces.”
  • Daylight models must contain at least one “daylight transition surface” or “daylight exterior surface” in order to compute daylight component.
  • The virtual exterior ground surface is automatically assigned a reflectance of 18% (average reflectance of an exterior scene, by Eastman Kodak, circa 1904).  

With these ideas in mind, we can create any model, classify all exterior surfaces as “exterior daylight surfaces” and classify all glazing as “daylight transition glass.” All interior surfaces may remain single- or double-sided, as created using the room or object tools, or imported (imported surfaces become objects). 

Courtesy: AGI website (www.agi32.com)



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
June 2018
Chilled-water system design, NFPA 99, Grounded power supply systems
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me