Teck acute care centre: improving health care resiliency

Reducing a building’s energy demand has long-term cost benefits and decreases the amount of fuel storage needed during the loss of power from the utility.

11/07/2018


Teck Acute Care Centre (Photo credit: Ed White Photographics)Resilience in the built environment involves reducing, adapting to, and mitigating risks. It refers to designing buildings to absorb the shocks of short-term disruptive events or long-term stresses while delivering optimal facility recovery. These shocks and stresses can be natural or human-induced and may include droughts, hurricanes, floods, earthquakes, pandemics, and chemical spills.

Seismic activity is a special concern for the West Coast of the United States and Canada. British Columbia's Provincial Health Service Authority (PHSA) wanted their new 640,000 square foot Teck Acute Care Centre (TACC) designed with stringent "post-disaster" resilient features, including an absolute energy target and three days of potable water storage.

Reducing a building's energy demand has long-term cost benefits and decreases the amount of fuel storage needed during the loss of power from the utility. To meet PHSA's goals, AEI designed an advanced heat recovery system consisting of water-to-water heat recovery chillers, air-cooled heat recovery chillers, and air-source heat pumps mounted within the warm exhaust air to boost efficiency. The heat recovery is then used as the first-tier building heating and domestic water pre-heat.

District hot water and campus steam are the second and third tier, respectively, supplemental heating sources. The mechanical plant and the air-handling system is sized for 100% outdoor air operations with 15% additional capacity. This allows for future clinical or long-term temperature changes.

Heat Recovery System (Illustration credit: Michael Schrader /  Affiliated Engineers, Inc.)Calculating and planning for domestic water storage

The governing codes and standards did not have a calculation methodology for potable water storage. AEI looked to the California Office of Statewide Health Planning and Development (OSHPD) standard for acute care facilities, which requires 50 gallons of potable water storage per day per inpatient bed. Reducing the daily water demand decreases the amount of water storage needed during the loss of water from the utility. AEI designed the plumbing system to use 35% less water than the LEED baseline building. The mechanical plant consists of all air-cooled or water-to-water heat recovery equipment so there is no demand from a cooling tower, further reducing the building's water storage requirement. An additional water savings strategy included chilled water effluent cooling on the sterile processing autoclaves. The waste heat from the effluent is also captured by the heat recovery system.

The domestic water storage design consists of two tanks that hold a day-and-a-half worth of water and can be refilled with pumper trucks.

Under normal operations, water from the public utility continuously flows through the tanks to prevent stagnation and includes a side-stream chlorination system. The owner also required 24 hours of sanitary sewer storage, and the building has two tanks with pipe connections so pumper trucks can remove waste.

Continuing care during a disaster

Water Storage (Illustration credit: Michael Schrader / Affiliated Engineers, Inc.)Other resilient design features include six pandemic outbreak patient wings, a three-lane mass decontamination shower, and an active smoke control system. When activated, the pandemic outbreak patient wings switch to negative pressure, the air-handlers switch to 100% outdoor air, and a conference room at the entrance to the wing can double as an anteroom. Drop-down curtains in the ambulance bay canopy can be used to quickly convert the area into decontamination showers. The active smoke control system allows for individual smoke compartments to be pressurized during a smoke event. This allows procedures to continue and ICU patients to remain in place during an event without the loss of heating and cooling airflow.

The building is the second phase of the BC Children's and BC Women's Redevelopment Project and is an important milestone in the renovation and modernization of the facility, serving the needs of British Columbia's most seriously ill children and most complex obstetrical cases. The facility includes single-occupant patient rooms, medical/surgical inpatient units, an emergency department, medical imaging and procedural suites, a hematology/oncology department, and a pediatric intensive care unit, as well as a high-risk labor and delivery suite and a neonatal intensive care unit. TACC was designed to meet LEED Gold certification requirements.


Sean Lawler, PE, LEED AP, project manager and mechanical engineer, Affiliated Engineers. This article originally appeared on Affiliated Engineers' blog. Affiliated Engineers is a CFE Media content partner.



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
November 2018
Emergency power requirements, salary survey results, lighting controls, fire pumps, healthcare facilities, and more
October 2018
Approaches to building engineering, 2018 Commissioning Giants, integrated project delivery, improving construction efficiency, an IPD primer, collaborative projects, NFPA 13 sprinkler systems.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me