Study: Fire caused WTC collapse

Following a three-year investigation, a government agency concludes that fire caused to the collapse of the 47-story Building 7 in the World Trade Center complex.

08/26/2008


The Commerce Department’s National Institute of Standards and Technology (NIST) has concluded that the 47-story World Trade Center (WTC) Building 7 collapsed on Sept. 11, 2001, primarily due to fire--the first known instance of fire leading to the complete collapse of a tall building.

“Heating of floor beams and girders caused a critical support column to fail, initiating a fire-induced progressive collapse that brought the building down,” said NIST WTC lead investigator Shyam Sunder. “Video and photographic evidence, combined with detailed computer simulations, show that neither explosives nor fuel oil fires played a role in the collapse of WTC 7.”

The report pointed to one key factor leading to the collapse: thermal expansion of long-span floor systems at temperatures “hundreds of degrees below those typically considered in current practice for fire resistance ratings.” Also, the report recommended stronger building codes and standards that ensure even in the face of severe fire and failure of fire-fighting systems, buildings remain standing.





Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me