Sports, entertainment venues: HVAC systems

Sports arenas and entertainment facilities involve complex engineering solutions. Five consulting engineers offer advice on HVAC, ventilation, indoor air quality, and more.

04/24/2013


Keith Cooper, PE, President, McClure Engineering, St. Louis. Courtesy: McClure EngineeringDouglas H. Evans, PE, FSFPE, Fire Protection Engineer, Clark County, Nevada. Courtesy: Clark County, NevadaBill Larwood, PE, LEED AP, Senior Vice President/Project Principal, Syska Hennessey Group, Los Angeles. Courtesy: Syska Hennessey GroupKevin Lewis, PE, LEED AP BD+C, Vice President, Henderson Engineers, Lenexa, Kansas. Courtesy: Henderson EngineersBruce McKinlay, Principal, Arup, Los Angeles. Courtesy: Arup

Participants (left to right):

Keith Cooper, PE, President, McClure Engineering, St. Louis

Douglas H. Evans, PE, FSFPE, Fire Protection Engineer, Clark County, Nevada

Bill Larwood, PE, LEED AP, Senior Vice President/Project Principal, Syska Hennessey Group, Los Angeles

Kevin Lewis, PE, LEED AP BD+C, Vice President, Henderson Engineers, Lenexa, Kansas

Bruce McKinlay, Principal, Arup, Los Angeles   


CSE: What unique requirements do HVAC systems have that you wouldn’t encounter on other structures?

McKinlay: For sports venues, large quantities of ventilation typically are required to meet occupancy demands. In addition, there are significant latent loads from the occupants. These factors normally require air handling systems to be designed with both humidification and dehumidification. In addition, the systems are often used intermittently and are required to bring the house to setpoints quickly after the arena fills up and lights are turned on. Because of the large ventilation loads, there is significant opportunity to save energy through air side heat recovery from exhaust air streams. This is typically done through run-around coils, air heat exchangers, and heat pipes.

Engineers at Arup worked on Miller Park, a 42,500-seat stadium that is home to the Milwaukee Brewers. The facility is among the first sports arenas to include a retractable roof and climate conditioning in the bowl. Courtesy: Tim GriffithEvans: HVAC systems also may be designed to provide smoke management functions. This can substantially complicate the HVAC design. The designers must determine if it is more cost-effective to have a dedicated smoke management system, or if it should be combined with the HVAC system. In order to design the smoke management system, the expected fire size must be taken into account. If the design intends to keep smoke above head height to allow safe evacuation, this can further complicate the smoke management design.

Larwood: Arenas with hockey games must maintain air with low humidity, which can be tricky considering that these venues’ doors are continually being opened before and during the event. We’ve approached these venues by sub-cooling the air to less than 50 F to remove moisture and then reheating to maintain comfort. Of course, security continues to be a factor in the design of HVAC systems for sports and entertainment venues—the location of outside air intakes should always be considered to minimized chemical threats.

Lewis: The biggest issue in sports and entertainment venues is typically the size and location of the units. Depending on where the units are located, you need very large ductwork to supply and return air. You also need a close proximity to an outside wall so you can provide a louver with the capacity to bring in adequate outside air. In most conditions, we typically work with custom air-handling unit (AHU) manufacturers to be able to work around structural and head height limitations and still provide an energy-efficient solution. Because our units are custom, it gives us design flexibility to provide the necessary cooling/heating and bypass coils to meet the supply demands of multiple event types.

Cooper: Dehumidification and high latent loads become typical considerations in many of these facilities. Large and varied uses may dictate unique air distribution challenges. Ventilation controls must be able to accommodate large swings in outside air requirements often over relatively short time periods. Pools demand special temperature, humidity, and air movement controls. They also present opportunities for energy recovery and demand close attention to vapor barriers.


<< First < Previous Page 1 Page 2 Next > Last >>

Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me