Sizing VFDs for optimal operating efficiency

A new control strategy and implementation system optimize variable frequency drive (VFD) efficiency to meet cooling-air requirements.

05/31/2016


Learning Objectives:

  • Explain the impact of variable frequency drive (VFD) enclosure parameters on VFD performance and operational reliability.
  • Analyze the VFD's efficiency and its ability to meet enclosure cooling-air requirements with the new control strategy.
  • Outline the new control strategy and implementation system developed to optimize VFD efficiency.

The VFD enclosure cooling-air fan should be sized by the mechanical engineer by considering cooling-air load, temperature entering the enclosure, and the allowable operating temperature. The enclosure cooling load is caused by the drive inefficiency, resulting in increased air dry-bulb temperature. Required cooling-air volume should be calculated assuming that the VFD enclosure load will be carried out as the sensible load only.

Figure 1: Relative design variable frequency drive enclosures’ cooling-airflow rates depending on maximum allowable enclosure operating temperature. Courtesy: Advanced Research TechnologyThe actual VFD enclosure cooling load during design and off-design conditions must be verified from monitoring data; otherwise, the enclosure cooling load could be substantially higher when compared with data from a VFD manufacturer. The actual enclosure-load deviation is due to the different patterns of the static and dynamic hydraulic-pressure losses in various systems. The design cooling-airflow rate (CAFRDES) will be determined based on the maximum anticipated ambient temperature (TAMB MAX) surrounding the VFD enclosure and by a manufacturer's allowable VFD enclosure maximum operating temperature (TOPR MAX).

Figure 1: Relative design variable frequency drive enclosures’ cooling-airflow rates depending on maximum allowable enclosure operating temperature. Courtesy: Advanced Research Technology

The following four equations determine major enclosure operational parameters in British system thermal units:

1. QDES/OFF-DES = QTOT = QSEN = 1.085 x (TEXT MAX - TENT MAX) x CAFRDES = 4.5 x ∆E x CAFRDES

2. CAFRDES = QDES / [1.085 x (TEXT MAX - TENT MAX)]

3. TOPR MAX = (TENT MAX + TEXT MAX) / 2

4. TEXT MAX = 2 x (TAMB MAX - TENT MAX)

Where:

QDES/OFF-DES, QSEN, QTOT = VFD enclosure design/off-design, sensible, and total cooling load

TENT MAX = Maximum anticipated dry-bulb cooling-air temperature entering the VFD enclosure; depends on the location of the enclosure (i.e., in the air conditioned area, in the area with mechanical-free cooling, etc.)

TAMB MAX = Manufacturer's allowable dry-bulb ambient air temperature surrounding the VFD enclosure, which represents the enclosure's maximum allowable operating temperature TOPR MAX

TEXT MAX - TENT MAX = Temperature differential between maximum cooling-air dry-bulb temperatures exiting and entering the VFD enclosure

∆E = Enthalpy differential for cooling-air exiting and entering the VFD enclosure.

Design cooling-air conditions entering the VFD enclosure are related to the design cooling-air dry-bulb temperature, relative humidity, air density, and humidity ratio.

Figure 1: Relative design variable frequency drive enclosures’ cooling-airflow rates depending on maximum allowable enclosure operating temperature. Courtesy: Advanced Research Technology

Because VFD manufacturers allow high dry-bulb temperature and relative humidity of cooling air entering the enclosure, the moist loaded air is always present in the enclosure. As indicated by the first equation, the enclosure's total cooling load should be equal to its sensible load. However, if the VFD enclosure design's cooling-air flow rate is specified in the equations, the enclosure's optimal operating conditions can be satisfied without a moisture exchange. If these specifications aren't met, it might result in moisture deposition in the enclosure.

Figure 1 demonstrates the impact of TOPR MAX on the design relative cooling-air (RCAFRDES). The TOPR MAX varied from 104° to 122°F. This is the conservative approach, because the actual TOPR MAX might be higher due to the TEXT increase associated with heat removal caused by a greater VFD power-loss factor. Compensating for the increase in TOPR MAX will require employing an oversized VFD. The higher operating temperature of the VFD enclosure will lead to increased TEXT MAX, which can be calculated in the last equation.

TENT MAX depends on the location of the enclosure and varies from 50°F for an air conditioned area to 100°F for mechanical-free cooling with a once-through ventilation system. The top graph in Figure 1 indicates that RCAFRDES is drastically reduced when TENT MAX drops from 100° to 90°F, which coincides with VFD enclosure cooling-air temperature differentials increasing from 8° to 28°F. A further reduction of TENT MAX and the correlated increase in the enclosure's temperature differential leads to a lower reduction of the design's relative cooling-airflow rate.

Figure 1 also indicates that, for the considered conditions, the maximum design cooling-airflow rate of 100% occurs at TENT MAX = 100°F and TEXT MAX = 108°F (i.e., at TOPR MAX = 104°F). The increase in allowable VFD enclosure operating temperature from 104°F (shown in the top graph of Figure 1) to 113°F (shown in the middle graph of Figure 1) leads to the reduction in RCAFRDES from 100% to 30.8%. It also causes the VFD enclosure's temperature differential to increase from 8°F (at TENT MAX =100°F and TEXT MAX = 108°F; see Figure 1, top graph) to 26°F (at TENT MAX =100°F and TEXT MAX = 126°F).

The further increase in allowable operating temperature from 104° to 122°F (shown in the bottom graph of Figure 1) leads to the additional reduction in RCAFRDES from 100% (see Figure 1, top graph) to 18.2%. It also causes the VFD enclosure's temperature differential to further increase from 8°F (at TENT MAX =100°F and TEXT MAX = 108°F; see Figure 1, top graph) to 44°F (at TENT MAX =100°F and TEXT MAX = 144°F).

Therefore, RCAFRDES could be noticeably reduced by lowering the cooling-air temperature entering the enclosure. The reduction of TENT from 100° to 50°F could lead to the RCAFRDES decreasing from 100% to 7.4% (shown in the top graph of Figure 1).

Given equal load conditions, the reduction in cooling-air temperature entering the VFD enclosure leads to an increased exiting cooling-air temperature, causing an increase of the temperature differential and correlated reduction in cooling-airflow rate. Maintaining a lower operating temperature at the same load and cooling-air temperature entering the enclosure will require a lower cooling-air temperature exiting the VFD enclosure and a higher relative airflow rate compared to the design magnitude (shown in the first graph of Figure 1).

Further analysis demonstrates how the cooling-air temperature exiting the VFD enclosure impacts the enclosure's operating temperature of 70°F and flow rate at constant entering-air temperature. A wide variety of operating temperatures, from 75° to 100°F, might apply by adjusting the VFD enclosure's cooling-airflow rate. For instance, the increase in the enclosure operating temperature from 75°F to 85°F will allow the reduction in cooling-airflow from 100% to 33.3%. The increase in operating temperature from 75° to 100°F will reduce required cooling-airflow from 100% to 16.7%.


<< First < Previous Page 1 Page 2 Page 3 Next > Last >>

Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
May 2018
40 Under 40 winners, fire and life safety, performance-based designs, and more
April 2018
VRFs, lighting controls, BIM coordination, and more
March 2018
Sizing water pipes, ASHRAE 90.1, recovering waste heat, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me