Selecting a fire protection system

Fire protection engineers must know what factors come into play when deciding on and recommending a fire protection system.

05/10/2013


Learning Objectives

  1. Understand the factors to consider when determining the need for specific types of fire protection systems.
  2. Learn how codes, standards, and other documents influence the choice of fire protection systems.
  3. Identify the importance of goal setting, loss tolerance, and the application of risk assessment techniques in deciding on fire protection systems. 

Clean agent fire suppression systems have long been the answer to protecting high-end equipment, electronics, and irreplaceable items from fire and the damaging effects of water. This Impulse Technology clean agent system is available with either ECARO-25A principal role of the consulting engineer is the design of building systems that satisfy the overall goals and objectives of his or her client. When it comes to fire and life safety, the fire protection engineer is called upon to design those systems deemed necessary for the project. 

Several questions might be posed: What systems are necessary? Is one type of system or systems more appropriate than another? Are redundant systems needed? Who makes this decision and recommendation, and what influences their thought process? 

Associating client goals with building, fire regulations 

Any building project is a significant investment and undertaken with specific goals and outcomes in mind. Once built, the structure serves the purposes and needs of its owners. The building and its associated systems enable the operations of the overall enterprise contained within, that is, provide a workplace, facilitate healthcare services, support manufacturing processes, shelter people and assets, and so on. 

To ensure that fire and life safety features are sufficiently considered and provided for in the design and construction of a building, governmental regulations come into play and must be adhered to. Therefore, one of the principal needs and goals of the building owner is identification of and compliance with the relevant building and fire regulations. Failing to comply with the applicable rules can prevent occupancy, delaying the use of the building and significantly impacting the overall return on investment. 

The intent of most building and fire regulations is to establish the minimum requirements for safeguarding public health, safety, and general welfare. The key term here is “minimum.” The following questions come to mind: Do the minimum requirements align with the goals and objectives of your client, and the intended operations of the enterprise? Are you confident the minimum requirements provide the desired level of life safety, property protection, continuity of business operations, or preservation of cultural resources should a fire occur? Has this decision been given proper consideration, and have the goals and objectives been adequately articulated? For instance, building regulations have traditionally addressed property protection only to the extent necessary for occupant and firefighter safety. How might this realization impact the overall implementation of the fire protection strategy during not only the design and construction process, but also throughout the life of the building?

It is worthy to note that while model codes serve as the basis for most building regulations in various jurisdictions across the United States, most jurisdictions and governmental agencies amend the various adopted versions of the model regulations, or enact bylaws that override the rules of the adopted model codes and standards. Thus, a uniform level of safety from fire is not necessarily prescribed nor implemented throughout the United States. 

The WFD60, a water flow detector, can be used with 6-in. pipe. This application was in a fire sprinkler closet protecting an office and warehouse. Courtesy: System SensorWhat do building regulations say about fire protection systems? 

Building regulations mandate active fire protection systems, largely automatic sprinkler systems, based upon the occupancy types associated with the building, the size and location of the fire area, and the expected occupant load. For instance, the International Building Code (IBC) requires automatic sprinkler systems in Group A-2 occupancies, such as restaurants, where one of the following conditions exists:

  • The fire area exceeds 5,000 sq ft.
  • The fire area has an occupant load of 100 or more.
  • The fire area is located on a floor other than the level of exit discharge.  

Similar requirements are found in NFPA 5000: Building Construction and Safety Code and NFPA 101: Life Safety Code. Additionally, model codes require sprinkler systems for certain types of buildings regardless of the occupancy type. For example, sprinkler systems are required for all high-rise buildings.

Building regulations also allow for “alternative automatic fire-extinguishing systems” or “other automatic extinguishing equipment,” but provide limited direction on when such systems are needed or should be considered. Depending upon the model code, these “alternative” or “other” systems are identified as wet chemical, dry chemical, foam, carbon dioxide, halon, clean-agent, water spray, foam-water, and water mist. Reference is normally made to the associated NFPA standards for the system under consideration for relevant design and installation provisions, such as NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems or NFPA 17: Standard for Dry Chemical Extinguishing Systems

However, when a building or fire regulation references an “alternative” or “other” system, it usually does so in the context of providing life safety for building occupants, usually as an alternative to the requirement for installing an automatic sprinkler system. 

Property protection and business continuity 

Depending on the facility or operation under consideration, certain fire protection standards do address fire safety beyond life safety and include provisions for property protection and business continuity. However, these standards are not necessarily mandated and referenced by the applicable building and fire regulations. The design engineer needs to be aware of these other standards and how they might impact the overall project and serve to satisfy the overall fire protection goals of the building owner. 

An example of such a fire protection standard is NFPA 76: Standard for the Fire Protection of Telecommunications Facilities. The purpose of NFPA 76 is specifically to provide a minimum level of fire protection in telecommunications facilities, to provide a minimum level of life safety for the occupants, to protect the telecommunications equipment, and to preserve service continuity. 

The design engineer also needs to be aware of any insurance company input, as these loss control and underwriting recommendations typically serve to address property protection and business continuity concerns. Even so, the agreed-upon level of fire protection for the facility still must be considered and gauged with that of any insurance company recommendations. The degree of property protection recommended by the insurance company is normally based on the policy purchased and the overall philosophy of the insurer, not necessarily the long-term objectives and needs of the building owner. 


<< First < Previous Page 1 Page 2 Page 3 Page 4 Next > Last >>

Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
April 2018
VRFs, lighting controls, BIM coordination, and more
March 2018
Sizing water pipes, ASHRAE 90.1, recovering waste heat, and more
January/February 2018
Sizing water pipes, ASHRAE 90.1, recovering waste heat, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me