Seasonal Equipment Beats Permanent's Payback

What began as a one-time summer rental is moving into its sixth season. In 1996, Toyota Motor Manufacturing in Georgetown, Ky., began renting chillers to maintain its assembly plant at 79°F. Five air-cooled chillers with a total 1,500 tons of capacity took the heat and humidity out of the ambient summer air.

06/01/2001


What began as a one-time summer rental is moving into its sixth season. In 1996, Toyota Motor Manufacturing in Georgetown, Ky., began renting chillers to maintain its assembly plant at 79°F. Five air-cooled chillers with a total 1,500 tons of capacity took the heat and humidity out of the ambient summer air.

Eventually plant managers undertook an analysis, the results of which showed that using the rental chillers for peak summer loads was more cost-effective than adding to the 25,000-ton permanent water-cooled chiller capacity.

With 7,800 team members working on two shifts five days per week, "we performed load calculations using the most current weather patterns, and determined that we would need an additional 2,500 tons of chiller capacity," says Gary Van Corp, a mechanical specialist for Toyota. "By using air-cooled rental chillers, we eliminated the need for adding cooling-water piping connections and temporary containment areas for a water-cooled system."

For three years, the company rented seven 2,500-ton chillers. Then, Toyota added 2,000 tons of permanent chiller capacity, but still rented five 300-ton-capacity units in 1999 and 2000. The annual rental period runs from mid-June through August, the time of peak summer power loads.

From Pure Power, Summer 2001.





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
May 2018
40 Under 40 winners, fire and life safety, performance-based designs, and more
April 2018
VRFs, lighting controls, BIM coordination, and more
March 2018
Sizing water pipes, ASHRAE 90.1, recovering waste heat, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me