School Calls for Chiller Upgrade

The children's center at Washington Elementary School in Sacramento, Calif., is open year-round, and with a number of classrooms lacking windows, there is a constant demand for cooling. High charges for peak usage, coupled with the inefficiency of old chillers, called for a chiller replacement.The school had been using a pair of air-cooled reciprocating compressor chillers that were 20 years old.

01/01/2001


The children's center at Washington Elementary School in Sacramento, Calif., is open year-round, and with a number of classrooms lacking windows, there is a constant demand for cooling. High charges for peak usage, coupled with the inefficiency of old chillers, called for a chiller replacement.

The school had been using a pair of air-cooled reciprocating compressor chillers that were 20 years old. The primary unit had a cooling capacity of 60 tons, while the secondary unit's capacity was 40 tons. The challenges were to provide efficient operation at varying loads, control the existing secondary chiller with automatic lead/lag operation and install a new, quiet primary chiller that fit on the existing concrete pad.

With design ambient conditions of 105°F dry bulb/71°F wet bulb, designers undertook a comparison of evaporative- and air-cooled chillers-based on the load profile and the unit delivering 45 tons-and determined that the evaporative-cooled chiller would deliver an operating savings of about 60 percent.

To learn more about ECDX-045 chillers from Dunham-Bush, circle 103 on the Reader Service Card.





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me