Rubber Rolling Mill Finds the Right Inverter

For more than a decade, a rubber rolling mill in the northwestern United States enjoyed great success using a 150-hp inverter on its main mill drive. With time, the drive eventually failed, introducing more than obvious problems. In seeking to replace the device, mill staff attempted to implement various new drives.

03/01/2003


For more than a decade, a rubber rolling mill in the northwestern United States enjoyed great success using a 150-hp inverter on its main mill drive.

With time, the drive eventually failed, introducing more than obvious problems. In seeking to replace the device, mill staff attempted to implement various new drives. Unfortunately, none of them worked quite properly. The search continued until a suitable 150-hp, general-purpose open-loop unit was found.

At first, mill personnel thought that the new unit might not be large enough, especially since staff anticipated a higher output level in the near future. However, during a temporary hook-up, the drive—which was delivered the same day it was ordered—immediately proved itself. It did not stall or approach current limit during heavy press operations. Importantly, it powered through a "double-fold" test without stalling and only reached current limit for short, intermittent periods.

Then, an acid test was performed by "triple folding" the material. Even the mill's old drive couldn't do this; in the past when attempting this feat, the mill had to be stopped and reversed with the material being cut away. The new unit struggled but made it through the process.

The mill continued to run on the temporary 150-hp unit until a larger unit was delivered. The lesson learned was that hp rating—usually a major selling point with inverters—is not the only factor and that amps and overload ratings should be given equal consideration.





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
June 2018
Chilled-water system design, NFPA 99, Grounded power supply systems
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me