Project profile: Henkels & McCoy headquarters emergency generator

In this project profile, engineering firm Henkels & McCoy added a back-up generator to power its facility during loss-of-utility events.

03/25/2014


Project name: Henkels & McCoy Headquarters Emergency Generator

Project type: Addition to existing building

Engineering Firm: Henkels & McCoy

Building type: Office building

Location: Blue Bell, PA, United States

Timeline: November 2012 - October 2013


Previous 5kV Main Switchgear, manufactured in 1974. All images courtesy of Henkels & McCoy.

Project goals

  • Provide a reliable, low-cost backup generator solution to power the Jolly Road facility during loss-of-utility events.
  • Provide H&M with additional revenue from PJM “Demand Response Program”. This includes being able to take H&M off-grid while the utility is still operating, using closed-transition switching.

Building details

There are two buildings on this property. One building contains 6,000 sq ft of automotive maintenance area, 14,000 sq ft of warehouse storage, and another 9,000 SF of office space. The other building contains about 46,000 sq ft of office space, plus a cafeteria and a large data center and copy center.

Project details

Engineering, Construction, and the Henkels & McCoy Maintenance Department designed and installed a 4kV, 750kW generator. Engineering and all concerned Newly completed substation yard and generator.worked with vendors to provide the most cost effective approach to this purchase and implementation. The generator was fed directly into a G&W Automatic Transfer Control Switchgear, which replaced the existing 35 year old switch. Requirements for participation in Demand Response Programs were evaluated; it was determined to be less important than providing effective, economic backup power.

Project success

The project's success was clearly demonstrated during the recent power outages in the area from an ice storm. When the area lost power, the entire Henkels & McCoy facility was able to stay powered up and respond with line crews and other personnel and equipment. In addition, the other employees could perform their work, reducing the amount of downtime and expenses related to sending employees home.


Henkels & McCoy, 985 Jolly Road, Blue Bell, PA 19422



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me