Preventing wet stacking

Prevention of wet stacking drives many of the details of generator testing requirements.

03/02/2015


Figure 4: Unburned liquid fuel mixed with carbon particles result in a gooey mess known as wet stacking. The liquid tends to run along the joints in the engine, which looks like engine seals have sprung a leak. Courtesy: Smith Seckman Reid Inc.

Generally, any mention of wet stacking generates a lot of questions. Wet stacking is a phenomenon that affects diesel engineson the steel side of the unit. Articles like this are read by people with electrical expertiseon the copper side. Prevention of wet stacking drives many of the details of generator testing requirements, so a brief description is presented here.

When a diesel engine runs at light load, its fuel rate is low, and it doesn't generate much heat with each power stroke. The cylinder walls stay relatively cool and don't support complete fuel combustion. The unburned fuel exits the cylinder as vapor and carbon particles. Vapor condenses in the exhaust system,and appears as a thick black liquid at the system exit ports-typically, the engine exhaust outlets and the turbocharger. Historically, the exhaust outlets were called "stacks." When liquid appears at the stack outlets, the engine is said to be "wet stacking."


Figure 4 shows a 1,000 kW diesel generator in this condition. Unburned liquid fuel mixed with carbon particles result in a gooey mess, and drip from the stacks and from the turbocharger. The liquid tends to run along the joints in the engine. The appearance is a bit frightening; it looks like every seal in the engine has sprung a leak. In its early stages, though, wet stacking isn't particularly serious. The cure is to run the engine at reasonable loads for an extended period, using a load bank or available building load, to evaporate the liquid and blow the soot out of the exhaust system.

Extended periods of operation at light load can have serious and expensive consequences. Piston rings don't scrape away the oil film on the cylinder walls, and the remaining oil above the rings is exposed to high combustion temperatures. Under those conditions, the residual oil forms a hard, nonuniform film,disrupting the close mating between the rings and the cylinder wall. Fuel can slip past the rings to contaminate the oil, and the gaps in the film can result in a loss of compression. The piston rings can no longer support the high pressures of the power stroke, and the engine can no longer develop its maximum output power. This phenomenon is called "cylinder wall glazing," and when it's severe, it can't be resolved with a high-load run. Severe glazing requires an engine rebuild, with re-honing of the cylinders or liners, to restore engine performance.

Repetitive operation at light loads results in unwarranted confidence in the generators, in that they continually pass tests but often can't deliver adequate power to their connected loads when the utility fails.


Tom Divine is a senior electrical engineer and project manager at Smith Seckman Reid Inc. He is a frequent contributor to Consulting-Specifying Engineer magazine and Pure Power, and is often a speaker at CSE Webcasts.



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me