Prescription for building automation and controls in hospital, health care facilities

Hospital and health care facility projects are especially important due to their sensitive nature. Engineers chime in on building automation systems (BAS), building management systems (BMS), and controls.

11/26/2013


Michael Chow, PE, CxA, LEED AP BD+C, Member/Owner, Metro CD Engineering LLC, Powell, Ohio. Courtesy: Metro CD EngineeringGeorge Isherwood, PE, Vice President, Peter Basso Associates, Troy, Mich. Courtesy: Peter Basso AssociatesMichael Lentz, Associate, RMF Engineering, Baltimore. Courtesy: RMF Engineering

Participants

Michael Chow, PE, CxA, LEED AP BD+C, Member/Owner, Metro CD Engineering LLC, Powell, Ohio

George Isherwood, PE, Vice President, Peter Basso Associates, Troy, Mich.

Michael Lentz, Associate, RMF Engineering, Baltimore


CSE: What factors do you need to take into account when designing building automation systems (BAS) for hospitals and health care facilities

Lentz: All major building equipment needs to be tied into the BAS and alarmed for malfunctions. This is due to the critical nature of the systems to function 24/7 and also due to most health care facilities reducing maintenance staff. Emergency power for the automated control system and local panels also needs to be accomplished. Again, due to the critical nature of the systems to function 24/7, the systems cannot shut down, and if the controls are not on emergency when power is lost, the units will not automatically restart after the 10-second delay.

Isherwood: Ease of service and the ability to understand the systems is crucial. Building controls are becoming more complex and maintenance staffs are being asked to do more with fewer resources. We need to make sure we design building control systems that will not become a burden on the staff, but a benefit. 

CSE: How does implementing BAS in an existing building differ from designing controls for a new building?

Isherwood: There are a significant number of small hospital systems that have been using the same BAS for years. Some of these networks will no longer be supported by basic operating computer systems, let alone the BAS system. Also, different manufacturers have opened different control protocols for tying into a BACnet or similar common language. These challenges are huge for small hospitals, from both a solution and a cost standpoint.



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me