Power management system enhances emergency response

Case study: A super-tall building in the Middle East.

03/20/2014


A super-tall building in the Middle East contains three levels of enclosed underground parking, a hotel with multiple ballrooms and restaurants, several floors of offices, and multiple residential and observatory levels. Seven floors will host the building’s mechanical, electrical, plumbing (MEP), and fire protection equipment, which will use district-chilled water as a cooling source and feature three main chilled water pressure zones.

The building’s generator power systems will serve the following loads: fire pumps, fire transfer pumps, firefighter elevators, emergency evacuation elevators, emergency lighting system, safety and alarm systems, stair pressurization systems, lobby pressurization systems, public corridor exhaust systems, refuge floor pressurization systems, garage exhaust fans, partial building cooling load and associated equipment, and partial refuge floor cooling.

Three base building generators are located in each plant to support the life safety systems. Two plants are interconnected, providing reliable redundancy and backup for the building’s emergency power distribution system.

Like other super-tall buildings, there is a discrepancy between the code-required peak design demand and the building’s actual peak power usage. To take advantage of the additional power capacity already designed into the facility, the building’s power management system is programmed to accommodate a second and third tier of MEP systems that will enhance building response in the event of an emergency. This includes the building’s garage exhaust and corridor exhaust systems, life safety equipment supporting cooling devices, and refuge floor cooling.

During a power outage and after life safety Category 1 and legally required Category 2 systems were activated, then the third category is potentially energized. The power blocks in the third tier will be assessed based on each individual block’s power requirements and power availability. For example, the underground garage system was designed with 14 individual zones and allocated to the third tier. Upon receiving a signal simultaneously, all exhaust fans within this zone and adjacent zones will be activated. After necessary garage exhaust systems are online, the next power block in the third tier could also be activated if there is ample power capacity.

 

 


Suzan X. Sun-Yuan is a senior associate and lead mechanical engineer with Environmental Systems Design. She has experience with super-tall buildings, food labs, and central plant designs and upgrades. Mohsen Aghai is a senior associate and lead electrical engineer with Environmental Systems Design. He has experience with super-tall, mixed-used, commercial, and governmental buildings as well as hospitals and central plant designs and upgrades.

 



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me