Narrow Band Signaling: A Clearer Option for Emergency Notification

08/01/2005


Needing to be heard is not always about making a lot of noise, but making the right noise. In 2002, the National Fire Alarm Code (NFPA 72) recognized the need for clear audible messages by including a new audible signaling requirement for optional use on fire systems. Called "narrow band signaling" this technology was designed as a cost-effective method for making emergency messages heard in high-noise factories and other industrial areas.

It works by reducing the number of audible appliances needed in noisy environments by issuing signals and voice messages at pre-determined frequencies that ride above the average ambient noise.

In addition, since narrow band signaling systems can be designed to be fully compliant with OSHA and NFPA requirements, the technology makes it possible to provide audible notification communications to areas where it was not feasible under the previous NFPA code.

How narrow band signaling works

The narrow band method is based on the fact that noise at one frequency range does not mask sound signals at other frequency ranges. Consequently, this new signaling method uses narrow (1/3) octave bands instead of broadband dBA to measure sound levels and ensure alarm signals exceed background noise by at least 10 dB in one of the octave bands.

Covered under section 7.4.5.1 in NFPA 72 (2002), this technology is also specifically cited as an alternative for conventional dBA methods. As a result, narrow band signaling can provide daily paging as well as emergency alarm signaling and voice messaging to noisy work areas that cannot be suitably supported by traditional communication systems. This is because many conventional dBA methods may not be feasible due to the number of speakers and the total wattage required to meet NFPA code requirements.

For instance, to meet the 15 dBA above ambient requirement in a 200 ft. × 400 ft. protected area with conventional speaker systems, cluster speakers would have to be spaced in a grid pattern every 28 ft. This would require an incredibly cost-prohibitive usage of 98 clusters utilizing 392 speakers at 5,880 watts.

In comparison, the narrow band method used within the same application would require far less speakers and power.

Another advantage to narrow band signaling is its ability to be customized or tailored so the audio message can rise above different noise levels. This is a particularly useful benefit to factories and plants that operate different machinery at varying noise levels throughout their facilities.

A wise choice

Combined with voice alarm and paging systems, narrow band signaling technologies not only offer ready compliance with strict regulations, but can also improve employee safety by supplying enhanced communications capabilities during emergencies as well as normal daily operations.

Conventional Narrow Band
Ambient Noise94 dBA83 dB @ 2,000-Hz band
Code - 3 dBA107 dB @ 10 ft.105 dBA @ 10 ft., 2,000 Hz
Cluster Spacing28 ft.Zero ft.
Total Clusters98 (392 speakers)15 (60 Speakers)
Total Watts5,880900



Benefits of mass notification

Clear, audible messaging in loud environments

Allows notification communication to areas where it was not feasible under previous NFPA code

Can provide daily paging as well as emergency alarm signaling and voice messaging



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me