Multi-Purpose Comfort for Multi-Use Stadium

As the home of four professional sports teams, the Staples Center in Los Angeles can experience up to 10 days each season where multiple events occur on a single day. Therefore, its 35-person crew needs to be able to change the venue from hockey to basketball in less than two hours, including installation or removal of extra seating.

01/01/2002


As the home of four professional sports teams, the Staples Center in Los Angeles can experience up to 10 days each season where multiple events occur on a single day. Therefore, its 35-person crew needs to be able to change the venue from hockey to basketball in less than two hours, including installation or removal of extra seating.

The facility's seating, concessions, lighting and sound systems were all designed to maximize a visitor's experience. Not so obvious to the spectators, but just as important for their comfort, is the HVAC system.

'Chill out' in L.A.

M.E. Engineers/Hayakawa Associates of Los Angeles designed a system that includes low chilled-water and supply-air temperatures and features three high-efficiency 833-ton chillers using HCFC-123. Cooling towers for the units are based on an 82.5°F to 94.6°F range and operate on a 2.3 gpm/ton flow rate. This design improves overall system efficiency by reducing pump and fan power requirements over more traditional 3.0 gpm flow rates.

The centrifugal chillers deliver chilled water in the range of 40°F to 42°F to the air handlers for most arena events, and at 36°F for hockey games and ice rink shows. Lower chilled-water temperatures during rink events assures dehumidification to help maintain the surface quality of rink ice. With this low temperature water, supply air is delivered to the space at 40°F for ice rink events and at 45°F for others.

In addition to the centrifugal units, a 300-ton screw chiller is used when chilled-water demand is low, typically at times when the arena is not in use.

Air handlers, with 12-row chilled-water coils, are the main source of dehumidification of building air. Other types of air handlers supply restaurants, retail areas, locker rooms and office areas.

In addition to general seating areas, there are 160 luxury suites, each with variable-air-volume boxes and electric reheat and ventilation air provided by a dedicated duct system.

Acoustical comfort

Guaranteeing the right climate is the major challenge for the HVAC system, but acoustical comfort is also a significant issue for HVAC designers. "We book a wide range of events, not just sports contests," explains Bill Pottorff, the facility's chief engineer. "It's important that ambient sound be held as low as possible."

In this respect, Pottorff says, the acoustical and comfort levels produced by the facility's plant has exceeded all expectations.





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
June 2018
Chilled-water system design, NFPA 99, Grounded power supply systems
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me