A Final Word on Cable Combustibility In response to the letter written by Dean K. Wilson (CSE 03/02 p. 9), regarding his article "Circuit Integrity Cable Re-Examined" (CSE 09/01 p. 55), as pointed out in his letter, indeed, circuit integrity fire-alarm cable was not shown in the Pyrotenax video, and we agree that the effect is less pronounced in this type of cable, simply because of the amount ...

07/01/2002


A Final Word on Cable Combustibility

In response to the letter written by Dean K. Wilson ( CSE 03/02 p. 9 ), regarding his article "Circuit Integrity Cable Re-Examined" ( CSE 09/01 p. 55 ), as pointed out in his letter, indeed, circuit integrity fire-alarm cable was not shown in the Pyrotenax video, and we agree that the effect is less pronounced in this type of cable, simply because of the amount of insulation involved.

However, the gases produced by decomposition of types MC and RHH cable under fire conditions should not be compared with those from conventional cables. One difference between these cables and other polymeric cables is the application in which they are used. These cables are intended specifically for critical life-safety circuits in buildings for equipment such as fire pumps and emergency generators.

The flammable gases they introduce during a fire are capable of being funneled directly into the emergency equipment enclosure, where an arcing contact could cause ignition. There are other differences, but on this basis alone—that emergency circuit wiring might introduce a hazard threatening the emergency power supply—there is a safety issue that needs to be addressed. Conventional cables are not used for fire-rated circuits, except as part of an electrical circuit protective system. There are 25 electrical circuit protective systems listed in the 2002 Fire Resistance Directory .

In should be noted that only the systems using ceramifiable insulation introduce the hazard in question. But any chance of a hazard occurring is too much of a chance to take when lives are at stake.

Barry O'Connell, P.Eng., Commercial Marketing Manager Tyco Thermal Controls (Formerly Pyrotenax Cable Ltd.)

Correction: In the news story "Halon Replacements Still a Hot Topic," (CSE 06/02 p. 16) the item incorrectly noted that the U.S. would be under mandate to replace Halon by 2003. The article should have reported that Europe was under mandate to do so. We apologize for the error.



Have something to say?

Send your comments to:

"Letters to the Editor"

c/o Jim Crockett

Consulting-Specifying Engineer

2000 Clearwater Drive

Oak Brook, IL 60523

Or email:jcrockett@reedbusiness.com



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
June 2018
Chilled-water system design, NFPA 99, Grounded power supply systems
May 2018
40 Under 40 winners, fire and life safety, performance-based designs, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me