Letters: Reader Feedback

Curbing contaminant carryover I was interested in and enjoyed your article "A New Lab Formula" (CSE 3/06, p. 24). I am curious about the heat wheel technology you refer to. How do you get around the cross-contamination between airstreams? GREG HOLMES, P.E., R.P.A. OPERATIONS MANAGER, JONES LANG LASALLE CORPORATE, PROPERTY SERVICES Michael J.

06/01/2006


Curbing contaminant carryover

I was interested in and enjoyed your article "A New Lab Formula" ( CSE 3/06, p. 24 ). I am curious about the heat wheel technology you refer to. How do you get around the cross-contamination between airstreams?

GREG HOLMES, P.E., R.P.A. OPERATIONS MANAGER, JONES LANG LASALLE CORPORATE, PROPERTY SERVICES

Michael J. Dausch, P.E., MBA, director of design and construction for Johns Hopkins School of Medicine in Baltimore, which employs multiple energy-recovery wheels, responds:

Johns Hopkins began by using a total energy-recovery wheel designed specifically for lab type environments by SEMCO, Inc. The wheel utilizes a 3-angstrom molecular sieve technology that has the capability of avoiding the transfer of airborne contaminants contained in the lab exhaust air. Other technologies do not have this capability.

We first initiated a pilot test site of this technology more than 15 years ago on a small laboratory requiring approximately 15,000 cfm of outdoor air. Our health and safety department tested this system extensively to ensure that contaminant carryover did not occur. The following year we constructed our first major laboratory facility using this technology to precondition approximately 400,000 cfm of outdoor air.

These systems, located in our Ross Research Facility, were recently tested for both recovery performance and contaminant carryover as part of a Labs21 presentation, which can be viewed at www.labs21century.gov/conf/past/2003/presentations/a3_fischer.pdf .

Despite years of operation, the findings confirmed that the recovery performance had not diminished. The independent air quality testing confirmed that recovery wheels did not transfer contaminants from the exhaust airstream into the supply airstream.

Since that time, we have utilized the 3-angstrom molecular sieve total-energy wheel for many major laboratory projects—over one million total sq. ft.—with great success. In addition, SEMCO has completed a significant amount of research to address the concern for desiccant wheel carryover, which you can view at semcoinc.com .

Not on the schedule

The sidebar "Improved Smoke Ventilation at Atlanta's Airport" ( CSE 4/06, p. 56 ) indicates a bad operating schedule! It is well-known that rotating machinery has maximum stress during starting.

These ventilating fans will last a whole lot longer if they are alternately run for a one- or six-month period instead of only a week!

RCA determined this for 1,000-hp air compressors in the early 1970s in Marion, Ind.

CHUCK MUHLEMAN, PRESIDENT (RETIRED), PRESS CONTROLS CORP., HUNTSVILLE, ALA.





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
October 2018
Approaches to building engineering, 2018 Commissioning Giants, integrated project delivery, improving construction efficiency, an IPD primer, collaborative projects, NFPA 13 sprinkler systems.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me