Letters: Reader Feedback

Power for security In the article “Quality Power for Security Systems” (Pure Power, Fall 2007, p. 17) the author gives “underground local metal structures (gas piping, for example)” as one of the legal ways of connecting a grounding system to the earth. The author refers to the National Electrical Code for the listing.

11/01/2007


Power for security

In the article “Quality Power for Security Systems” (Pure Power, Fall 2007, p. 17) the author gives “underground local metal structures (gas piping, for example)” as one of the legal ways of connecting a grounding system to the earth. The author refers to the National Electrical Code for the listing. But according to NEC Article 250-52(a), “a metal underground gas piping shall not be used as a grounding electrode.” Can the author expand on this?

Igor A. Altshuler Engineer Baltimore via the internet

Author responds:

Indeed, you are most correct. The statement should have read “Other local metal underground piping (except gas lines).” Likewise, tanks that have been used to store explosive or hazardous contents should not be used as supplemental grounding electrodes. An acceptable example would be an abandoned underground metallic water storage tank that has been filled with moist sand.

Jay Adams Applications Engineer Transtector Systems Shayden, Idaho

Energy efficiency

The story “The climate has changed for energy efficiency” ( www.csemag.com , 10/22/07) said that “the energy used by commercial and industrial buildings in the United States is responsible for 45% of the nation's greenhouse gas emissions.” This is encouraging for the potential to make a big dent in those emissions. Although most domestic and non-domestic buildings are very wasteful of energy, in many ways that waste is easier to tackle in non-domestic buildings: First, the energy bill is usually much higher in non-domestic buildings, so there are greater financial rewards to be achieved by investing time into improving energy efficiency. There's a big economy-of-scale effect in the savings that can be achieved by investing time into energy management.

Second, the larger the building, the greater the chance that it already has interval metering equipment and access to interval energy data from that equipment. For buildings that don't have such equipment, the larger they are, the greater the payback from investing in such equipment. Analysis of such interval energy data for energy management purposes can easily lead to identification of huge sources of energy waste that would be very difficult to find without that data. Admittedly, these benefits will spread into the domestic sector as interval metering catches on there. Ultimately, the greatest energy saving are from motivating people to do their bit. This can be difficult in a work or home environment, but initiatives such as the Kilowatt Crackdown can make a huge difference.

Martin Bromley Energy Management Consultant via the internet





Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me