Is There a Future for Underfloor Air?

While high-technology facilities have long pioneered the use of raised-floor systems, there is scant agreement among engineers that underfloor air plenums are the next logical step.The rising heat-load densities of computer and telecommunications equipment-and the need for increased processing speed in a smaller box-is driving the use of underfloor air technologies, says Marc Anderson, P.E.

01/01/2001


While high-technology facilities have long pioneered the use of raised-floor systems, there is scant agreement among engineers that underfloor air plenums are the next logical step.

The rising heat-load densities of computer and telecommunications equipment-and the need for increased processing speed in a smaller box-is driving the use of underfloor air technologies, says Marc Anderson, P.E., of Syska & Hennessy. "We expect the telecom industry, which traditionally uses free-discharge or overhead ducted systems, to begin using raised floors, [because] the limits of traditional air-delivery methods will soon be reached," he observes.

On the other hand, underfloor systems help deliver what high-tech firms desire: increased airflow, colder discharge temperatures and alternative cooling strategies-such as an increased room-temperature gradient from floor to ceiling and a greater delta T across the coil. Also, in computer rooms where heat dissipation densities are high and relatively constant-or where computer equipment takes in cooling air from below-air from the access floor may work best, adds Calvin Witt, P.E., senior mechanical engineer for Roanoke, Va.-based Hayes, Seay, Mattern & Mattern.

Still, the barriers are significant, say engineers, and include occupant comfort-and cost.

"The prime barrier for most of our clients is the first cost of the raised-floor system and the associated appurtenances: structural equipment stands, grounding, underfloor smoke detectors and plenum-rated cable," says Anderson.

"The industry has introduced special fan-powered diffusers and even systems furniture with individual fans, ducting, integral air outlets and under-desk radiant panel heaters," adds Witt. "However, we believe that projects are rare where the cost of this additional flexibility is justified."

"Designs that employ [those] special features built into systems furniture require extensive design coordination, which is often complicated when the furniture is procured under a separate contract," adds CUH2A's Steven R. Rafferzeder, P.E.

When used, however, the engineers warn of recurring design issues:

  • Plenum height. Minimum access-floor depths-usually two feet or more-are critical for ensuring good airflow through the perforated tiles while accommodating additional cabling and piping, says Witt.

 

  • Airflow restrictions. Designers must take care not to choke off underfloor airflow, says Anderson. Underfloor restrictions-piping, conduit and cable-should be placed away from the discharge of precision AC units and preferably routed along the perimeter.

 

  • Temperature and humidity. "Design issues that require special attention include thermal decay at increased distances from the air-handling unit, perimeter heating, and condensation prevention with higher supply-air temperature," adds Witt.

 

  • Good seals. "Other criteria include sealing the plenum airtight," says Anderson. "This is especially true for underfloor gaseous fire-suppression systems, which depend on the ability of pressurizing the underfloor space."

Flexibility is the greatest benefit of these systems, say designers. When done well, underfloor-air-plenum, raised-floor systems pay for themselves quickly as compared to ducted systems, adds Anderson. "It only takes one major change in the equipment layout on the floor to realize this."





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me