Is it water or orange juice?

11/12/2010


Dear Control Engineering: I am working in the process to automate a pasteurizer. I am looking for a sensor technology to detect the change from water to orange juice, and from orange juice to water in the output process. It has a color sensor, but it doesn't detect the change all that well. Do you know a better sensor? Thank you. –Erick

When looking at a question like this, we have to think about how water is different from orange juice, and then which of those differences is the easiest to detect or quantify. Apparently color, the most obvious choice, isn’t good enough, so what are some of the other possibilities? Orange juice is more acidic and has more sugar in it, so those might be more practical to detect. I asked Jim Gray, application manager at Rosemount Analytical Instruments for some suggestions. He says, “I think conductivity using a toroidal sensor would be the way to go. That would be the easiest from a maintenance standpoint. The conductivity of OJ should be greater than the conductivity of water, although I don’t have any number handy. The problem with pH would likely be the sensor drying out when the process is down. A Coriolis flowmeter would provide a continuous inferential measurement of concentration but is much more expensive. Conductivity should be sufficient for a status indication.”

A toroidal conductivity sensor.A toroidal conductivity sensor is a doughnut-shaped probe that inserts into the process liquid stream. The toroid itself has two coils. One is powered and creates a magnetic field. The second is a receiver. The current induced in the receiver is in proportion to the conductivity of the surrounding liquid. The probe can be encased in an appropriate grade of plastic to withstand the process liquid. Units are available that are designed for sanitary applications in food processing.

--Peter Welander, pwelander@cfemedia.com



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me