I/O Modules: Product research and advice from Control Engineering subscribers

I/O module research shows that Control Engineering readers want modular, easy-to-use, rugged I/O, with many analog, digital, and networking options. Manufacturers say new I/O modules pack in those features. See more results, advice, products. NEW: PDF research report attached April 2.

02/01/2010


LINKS
More on I/O modules from Control Engineering , below:
-I/O module advice from survey respondents, vendors
- Respondent vendor, network protocol preferences - Control Engineering research report- PDF format
-I/O products & photos: Banner Engineering, Beckhoff Automation, Emerson Process Management, GE Intelligent Platforms, Invensys, Pilz, Turck, Yokogawa, and others.
Leave your view: What are your most significant I/O module-related issues? Please use the TalkBack feature at the bottom of the page.
I/O connectivity: Mostly PLCs

Control Engineering readers offered advice about I/O modules trends, use and capabilities in an online survey emailed on Jan. 7 to subscribers of the Control Engineering System Integration, Machine Control, and Process and Advanced Control eNewsletters.
By Jan. 11, 506 survey respondents represented a “next project” I/O count of more than 389,850 I/O points, an average of more than 770 I/O points each.
Most-needed I/O module features are digital and analog capabilities, and a design that plugs into a base or rack, snaps on more points, and can mix digital and analog. Also popular are capabilities for use within an enclosure, diagnostics, optical isolation, and easy expansion. Finding the right mixture of discrete, analog, and high speed I/O for specific applications, within budget, is a key challenge, agreed Jeff Payne, PLC, I/O and PC control product manager for AutomationDirect. Payne said vendors offer high I/O density of 32 and 64 points. Tighter designs save users’ money, Payne says.

I/O module: Leading features


 

In one example, Ingersoll CM Systems Inc.’s next generation deep fillet rolling machine saved 60% in costs compared to previous I/O modules, said Gary Munger, Ingersoll controls engineering manager. Savings came with fewer machine components and use of more economical Balluff IO-Link hubs. Fewer components also reduced the possibility of failures, Munger said.

 

Smart I/O modules

I/O module vendor loyalty

Programmable logic controllers account for most I/O connections, survey respondents said, more than three times the next largest connection, a distributed control system (DCS) or process automation system (PAS). Vendors have responded with wide-ranging connection capabilities. Omega Engineering’s Universal Remote I/O Modules connect to any PLC, the company says, offering up to 31 I/O modules daisy-chained per RS-485 link. They’re DIN-rail mountable, have optical isolation, and, at 0.69-in. x 3.94-in. x 4.72-in. (17.5 x 100 x 120 mm), can fit in small panels.

 

Survey respondents said industrial Ethernet and Ethernet connections account for more than half of network protocols used, followed by fieldbus, device-level, sensor-level, and wireless networks. Wireless designs are also said to resolve other issues.

 

Simatic ET 200pro IWLAN from Siemens Industry Inc. saves significant communication cabling and installation costs with wireless connectivity from any distributed I/O station and modules. The rugged IP67-rated design can be machine-mounted, without an electrical enclosure, Siemens says.

 

Nearly one-third (30%) of respondents said they use I/O modules with embedded intelligence to replace another controller. New I/O offerings for Eaton Logic Controllers (ELC) have smart I/O adapter modules that enable distributed I/O with limited local logic control. ELC distributed I/O communicate via EtherNet/IP and Modbus TCP Ethernet protocols, Modbus RS-485, and DeviceNet.

 

Opto 22 Snap Tex jacketed, pre-wired cables connect modules to field devices, terminal strips, and breakout boards.
Opto 22 Snap Tex jacketed, pre-wired cables connect modules to field devices, terminal strips, and breakout boards.
Phoenix Contact Busable 900 MHz radio provides simple I/O data connection, part of the Trusted Wireless Ethernet (TWE) industrial wireless portfolio.
Phoenix Contact Busable 900 MHz radio provides simple I/O data connection, part of the Trusted Wireless Ethernet (TWE) industrial wireless portfolio.
National Instruments cRIO-9022 Real-Time Controller uses an NI 9144 chassis to expand I/O module selection beyond 8 slots.
National Instruments cRIO-9022 Real-Time Controller uses an NI 9144 chassis to expand I/O module selection beyond 8 slots.

Write-in advice: Plan ahead...

Respondent write-in advice covered vendors, price, quality, lifecycle, networks, power and grounding, testing, and more. Respondents said to involve the owner early during the selection process; keep it simple; and leave room for spare I/O and slots. Develop standards for wiring and tagging wires, another said, and look at conversion rates to ensure they match control requirements. Look for distributed capabilities to place the I/O close to point of use and minimize installation and commissioning time.

 

What networks do you need your I/O systems to support?

Check all that apply. Base: 505 replied.

% / Protocol type / No. responses

62% Industrial Ethernet protocol 316
51% Ethernet protocol 259
39% Fieldbus protocol 196
32% Device protocol 163
24% Wireless protocol 119
18% Sensor-level protocol 91

Update: Due to a spreadsheet oversight, the print edition listed wireless response at 57, about 11%. Actual was 119 respondents, about 24%.

Source: Control Engineering research

 
Size of next I/O project

 

Study usage, location, customer requirements and future expansion plans. When sizing, determine how the finished control project should look in a drawing, identify physical points, separate by point type and signal used, compare with available points, and add necessary control hardware to connect the rest of the points.

 

Regarding networking and diagnostics, the biggest issue, said one respondent, is “the addressing between the I/O and the attached device. It seems that almost every vendor has its own addressing scheme. Use care and look into compatibility and ease of communication between devices.”

 

Remote I/O has come a long way for simplicity of configuration, update speed (now in real time), and cost effectiveness. Do research and take advantage of the new protocols, especially Ethernet-based ones, another said. Pressing I/O module-related issues are tied to protocol compatibility, ability of a node to multiple I/O types, and I/O module sizes, agreed Charlie Norz, product manager, Wago-I/O-System. Some products communicate in more than 16 protocols, Norz said, and save space inside machines.

 

 

 

Allen-Bradley 1762 I/O modules from Rockwell Automation expand connections to MicroLogix 1100, MicroLogix 1200 and MicroLogix 1400 controllers.

Allen-Bradley 1762 I/O modules from Rockwell Automation expand connections to MicroLogix 1100, MicroLogix 1200 and MicroLogix 1400 controllers.

On lifecycle issues, respondents said to leave room for expansion later and check how long current models will be in production and have support. Also ensure application engineering support and documentation are in the local language. A broad choice of I/Os is preferred. International standard programming, IEC-61131-3, is “very preferred.” ABB says its AC500-eCo I/O modules are easy to maintain, have a wide range of expansion modules, and the related controller uses IEC 61131-3.

 

 

Schneider Electric Modicon M340 PAC has discrete high-density I/O modules for up to 64 channels per module; analog I/O has up to 8 channels per module.

Schneider Electric Modicon M340 PAC has discrete high-density I/O modules for up to 64 channels per module; analog I/O has up to 8 channels per module.

Regarding power and grounding, noise problems can be avoided by using linear power supplies in lieu of switching power supplies. I/O should be hot swappable, not require downloads after connection, have channel-to-channel isolation, be G3 compatible, and have less power dissipation. “Along with isolation to remove ground loops,” said Bill McGovern, national sales manager, Dataforth Corp., input protection guards against over-voltages, while noise filtering serves to remove unwanted frequencies from I/O signals.

Honeywell Series C I/O has sleek styling for smaller footprint, easier installation and maintenance, longer life, and redundancy, if needed.

Honeywell Series C I/O has sleek styling for smaller footprint, easier installation and maintenance, longer life, and redundancy, if needed.

More on I/O modules from Control Engineering :
- Balluff-I-O hubs save machine builder 60%: Balluff IO-Link ;
- Banner-Wireless Banner Engineering working with Nivis to offer ISA100, WirelessHART ;
- Beckhoff-IO terminal EtherCAT interface for RTD temperature sensors ;
- Emerson - Updated control system rethinks field device connectivity and human interface ;
- GE Intelligent Platforms TranSphere TS Wireless I-O ;
- Invensys-Intrinsically safe I-O subsystem simplifies hazardous area ;
- Machine builder wins control panel design contest 60% less space, 30% less wiring ;
- Pilz - BMW uses Pilz decentralized I-O system, PSSuniversal ;
- Turck - RFID slice Turck BL67 modular distributed I-O system has a Simple RFID (RFID-S) ;
- Weidmuller-Wireless connectivity line ; and
- Yokogawa-Controllers DAQstation anniversary charts evolution of chart recorder - external I/O modules .

Also read:

- ABB AC500-eCo I/O modules can grow with the application , are easy to maintain, and offer a wide range of expansion modules, basic to advanced.

- I/O modules: Find the right mix, says AutomationDirect - I/O buyers are challenged to find the right mix of discrete, analog, and high speed I/O modules and remain within budget, company says.

- Dataforth DSCA DIN-rail mount isolated analog signal conditioners : Morethan 370 models of Dataforth DSCA isolated analog DIN rail mount signalconditioning modules are said to provide Dataforth Instrument Classperformance, outstanding accuracy, 3-way isolation, and pluggable screwterminal disconnects to simplify wiring and maintenance.

- Eaton Logic Controller input/output adapter - Eaton announces new I/O and I/O adapter offerings for Eaton Logic Controllers (ELC).

- Honeywell Series C I/O leverages the success and experience gained with port-mapped I/O to produce a unique design, the company says.

- National Instruments: 3 distributed I/O hardware platforms - Deterministic Ethernet Expansion Chassis, Ethernet/Serial Expansion Chassis, and Wireless and Ethernet Data Acquisition.

- Omega Engineering Universal Remote I/O Modules - HE359 Series provideS remote I/O for programmable logic controllers (PLCs); the application is no longer dependent on controller choice.

- I/O modules should be high density, easy to wire and configure, and reliable: Opto 22 - Opto 22 says density, ease of wiring, reliability, and auto-recognition setup software are must-have I/O module features.

- Phoenix Contact calls Axioline‘world's fastest I/O system' - Slow I/O? Blending Ethernet technology with terminal blocks, Phoenix Contact created the fastest available I/O speed, the company said at the Axioline I/O system introduction.

- Applications, lifecycle are I/O concerns, Rockwell Automation says - Resolving application-related issues and total cost of ownership are among customers' I/O-related issues, says Rockwell Automation.

- Keeping a low profile and being dense is OK, if you're an I/O module - Schneider Electric says I/O modules need to take up little space in the cabinet and offer a wide variety of voltage and current values to fit application needs. Distributed I/O on a machine can reduce wiring costs.

- Protocol compatibility, multiple I/O types : Wago - I/O module compatibility, ability of a node to accommodate multiple I/O types, and I/O module size, are important I/O topics, says Wago.

More graphics, research results on I/O Modules

Control Engineering Research Report: 2010 February I/O Modules offers more graphics and survey information not published in this article.



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me