Integrating electrical safety with design

03/08/2013


Electrical product design

U.S. electrical product specifications are developed in correlation with the NEC. While this can permit a safe electrical installation, it may not address worker safety issues when equipment has to be accessed or maintained after it is commissioned. While product standards are designed to provide guarding from electrical shock, in most cases they may not provide adequate safety from arc flash and arc blast. Once a cover or panel trim is removed, the equipment is not in compliance with the product standards and the worker could be exposed to electrical hazard.

Figure 4: A main circuit breaker is encapsulated so staff is not exposed to energized parts. If a listed and labeled design were approved so that the panel cover could be removed and be classified as de-energized with the main breaker in the panelboard loElectrical distribution equipment could be designed to isolate sections of the equipment in order to permit work on them without exposure to electrical hazards. Consider, for example, an electrical power panelboard. Typically, the main circuit breaker is unguarded and is located in the same compartment as the branch circuit breakers and wiring. If a listed and labeled design were approved so that the panel cover could be removed and be classified as de-energized with the main breaker in the panelboard locked out (see Figure 4), it would permit modifications and additions to the electrical panel in accordance with OSHA regulations. This would be an exceptional benefit for the residential market.

OSHA enforcement regulations forbid compliance officers from approving products or installations. They have to conduct inspections and review products in accordance with their listing and labeling. In the case of a residential panelboard, if there is electrical power on the line side of the main circuit breaker and the main breaker is in the off position, the panelboard is still classified as the worker could be exposed to live parts. Under the listing and labeling criteria, the employer would have to demonstrate that the equipment would be listed and labeled with live power inside and the cover removed. The manufacturers require all trims and covers be installed when there is power above 50 V present. The trims and covers act as guarding from live parts.  

The past 20 years have seen a marked evolution in the electrical industry's awareness of electrical safety issues and increased requirements for electrical safety-related work practices. Building inherently safe design into electrical products for maintenance and modification as well as installation purposes is the next step.

Engineers can design the hazard out of work tasks by specifying electrical products that have enhanced safety features, by specifying products that address both design requirements and operation of the facility, and by incorporating improved installation techniques is a strategy that will not only increase worker safety, but also increase productivity and profits.


Kenneth Mastrullo is president of MES Consulting Services. His many years in the electrical construction industry include: 7 years in OSHA's New England Regional Office (Region I Electrical Technical Expert), 6 years in the NFPA (Secretary, NFPA 70E Electrical Workplace Safety), and 11 years as a facilities engineer.


<< First < Previous Page 1 Page 2 Page 3 Next > Last >>

Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me