Industrial-strength design: Electrical, power, and lighting

Manufacturing and industrial facilities tackle heavy-duty projects during their day-to-day operations—so it makes sense that engineers working on such structures face a number of tough challenges. Engineers offer advice on how to achieve results when designing electrical, power, and lighting systems.

06/30/2015


Respondents

Jerry Bauers, PE, NEBB Qualified Professional, National Program Executive, Outcome Construction Services, Kansas City, Mo.

Jason R. Gerke, PE, LEED AP BD+C, CxA, Mechanical and Plumbing Group Leader, GRAEF, Milwaukee

Mark O’Connell, PE, Manager of Facilities Engineering, Matrix Technologies Inc., Maumee, Ohio


CSE: Describe some recent electrical/power system challenges you encountered when designing a new building or retro-commissioning an existing facility.

O’Connell: We have substantial experience with projects where existing facilities have been repurposed into a new manufacturing or process area. Sometimes, we find that the building’s electrical distribution documentation is nonexistent or outdated. This documentation is important in determining the existing electrical loads that need to maintain service, while adding additional loads associated with the new process. In addition, it is critical to review the electric utility or existing building infrastructure to determine if the system has the capacity to accommodate the proposed electrical loads. Finally, the engineer must develop a plan that incorporates new electrical improvements while maintaining existing building or plant operations. We feel strongly that communication with the owner is extremely important to ensure planning and coordination throughout the project design and installation

CSE: In your experience, what percentage of manufacturing/industrial facilities are transitioning to LED lighting?

O’Connell: We see a low percentage of manufacturing/industrial facilities that use LED lighting. The positive aspect is the use of LED lighting was nonexistent only a few years ago, so progress is being made. We are optimistic that LED lighting is building momentum due to the lower cost of LED fixtures, combined with manufacturers focusing more on their sustainability initiatives. As the cost of LED fixtures continues to decline, we expect LED lighting to increase significantly in market growth.



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me