Ice Improves Industrial Utility Rates

When Interpolymer Corp. decided to locate its new manufacturing facility near Boston, the maker of polymer dispersions had to find a way to avoid demand charges of $24 per kW on peak and $12 per kW off peak.

11/01/2000


When Interpolymer Corp. decided to locate its new manufacturing facility near Boston, the maker of polymer dispersions had to find a way to avoid demand charges of $24 per kW on peak and $12 per kW off peak. In developing a suitable mechanical system for the plant, the company found that the use of an ice thermal-storage system would bring electric costs in line with their operational and budgetary needs.

The system design incorporates two thermal-storage units, specially designed cooling towers and two 105-ton low-temperature reciprocating chillers. Ice is produced at night and in the early morning, and cold water is distributed from the storage units to two heat exchangers during the day for process refrigeration and comfort cooling.

The thermal-storage units feature a control mechanism that limits ice thickness and, therefore, the amount of ice generated to the required level for a given day's use. Typically, about 20 percent to 40 percent of capacity is made during winter months, as opposed to as much as 80 percent in the summer.

The company also employs a free-cooling cycle during colder months, allowing warm process water to circulate through the cooling tower to be chilled for use in the process-cooling loop.

For more information on the ice-storage systems employed in this project, circle 100 on page 91.





Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me