How to design high-efficiency hot-water systems for hospitals

Boilers for heating and domestic hot-water systems are used in many hospitals and health care facilities. This looks at the codes and standards that regulate boiler specification, plus energy efficiency and efficacy of hot-water heating systems.

10/24/2016


This article is peer-reviewed.Learning Objectives:

  • Identify requirements for a boiler system for heating and domestic hot water in a health care building.
  • Analyze the codes, standards, and other requirements for designing boiler systems and their related HVAC equipment.
  • Develop a design to maximize energy efficiency.

Hospitals offer a unique opportunity to be creative when designing a hot-water system. While providing reliable support for critical health care functions is the first priority, it is possible to design a system that significantly improves energy efficiency and cost-effectiveness by separating steam and hot-water systems and using condensing boilers configured to operate with maximum efficiency.

More than any other building type, airflow quantities in a hospital are dictated by code. Many of the spaces have minimum airflows regardless of the actual loads or the number of occupants. The Facility Guidelines Institute’s (FGI) Guidelines for Design and Construction of Hospitals and Outpatient Facilities” is the primary guideline being used today for hospital accreditation by The Joint Commission, and many states have either their own amendments or a complete alternate code.

FGI now references ASHRAE Standard 170: Ventilation of Health Care Facilities for the actual airflow requirements. All of the health care HVAC-related codes concentrate on the minimum acceptable airflow quantities for each type of space and the pressure relationship between the spaces. The codes also dictate the amount of air that is fresh outside air. Different systems have been used over the decades to meet these requirements, including constant-volume single zone, constant-volume multizone, dual-duct systems, and single-duct variable air volume (VAV) systems. In recent years, newer systems have been developed and tested including variable refrigerant flow systems and chilled beams. The majority of the health care facilities built within the last 20 years use a VAV system with hot-water reheat; therefore, this article will use this type of system as a basis for discussion.

VAV systems

When a VAV system is used in a health care facility project, the minimum airflow of the terminals is dictated by the space’s minimum airflow requirements. A portion of the terminal units is actually designed as constant volume terminal units, because the minimum airflow requirement exceeds the airflow required to meet both the heating and cooling load of the spaces. This results in the need for reheat all year. Coupled with the fact that domestic hot-water uses are constant throughout the year, a typical hospital may have a summer water-heating load that is two-thirds of the winter hot-water-heating load.

Hospitals, especially large ones (>500,000 sq ft), have an inherent steam requirement for sterilization-related equipment and the humidification of large outside air quantities. Because a steam system is necessary to begin with, there is a tendency to make it support a host of building functions. Historically, the steam system has been used to serve all functions requiring heat. These additional building functions can include kitchen, laundry, and typically all water heating. Domestic hot water and heating hot water are generated with steam using shell and tube or tank bundle-type steam converters.

This makes the steam system a major component of the facility, requiring trained and experienced boiler operators. Field-built water-tube boilers and manufactured water- and fire-tube boilers from 500 to 2,000 hp or more are present at most large hospital campuses. The inherent design of these boilers as noncondensing limits their efficiency, even in ideal conditions.

The age of the boiler, steam trap maintenance, and steam leaks all contribute to making the actual efficiencies of these systems much lower. Redundancy and system reliability have traditionally far outweighed any concerns over minor efficiency losses. However, times are changing, and an increase in efficiency of just a few percentage points is highly sought after.

Figure 4: A health care facility incorporates the use of modular condensing boilers to optimize energy consumption.Improving efficiency

A key strategy to improve the efficiency of heating systems for hospitals is to separate the heating water and the steam systems. In this new design paradigm, steam systems are downsized to meet only the direct steam requirements for humidification and sterilization. Hot-water systems for both domestic and hydronic heating, which had typically been generated through steam converters, are generated independently of the steam system using their own fuel source. This single measure—providing separate water boilers of the condensing type—gains several percentage points of efficiency for a large percentage of the facility heating needs. In addition, decoupling the heating-water systems from the steam system provides significant opportunities for the design professional to be creative when developing the most efficient system possible.

Condensing boiler efficiency is maximized when the temperature of the heating water returned back to the boiler is reduced below the dew point of the water vapor in the exhaust gases, which occurs at approximately 130°F. Condensing boiler efficiency improves as the inlet water temperature decreases, according to ASHRAE. The lower heating-water temperature causes the water vapor in the exhaust gases to condense. The condensate is then passed through a heat exchanger within the boiler, and the latent heat is recovered. In a conventional boiler system, this situation must be avoided because the condensate and residual air that remains after the combustion process causes damage to the boiler in the form of corrosion, failed refractory, and fin blockage due to sooting. While these potentially damaging conditions are still present in a condensing boiler, the boiler components and flue are constructed with corrosion-resistant materials to prevent corrosion and destructive effects.

These efficiency characteristics encourage the designer to drive the heating-water-return (HWR) temperature as low as possible. The first step is to evaluate the climate conditions to identify if the hot-water system can be designed to operate at a supply temperature that is closer to the exhaust gas condensing point. Ideally, the system can be designed to work with 140°F supply temperature with an HWR temperature within the 110 to 120°F range on a design heating day. These operating temperatures are especially practical in southern climates with milder winters.

However, designing with a lower hot-water temperature requires a careful analysis of the system heating coils. The lower hot-water temperature causes a reduction in “approach,” the term given to the difference between the hot-water-supply temperature and the temperature of air entering the heating coil. Due to the lessening of the approach, more coil surface area is required to obtain the same heating capacity versus when 180°F water is supplied to the reheat coil. To counteract this reduction in coil capacity, three-row coils may be required.

Another potential solution is to upsize the terminal box to increase the coil surface area. For example, a 6-in. terminal box with a two-row coil may be adequate to meet the airflow requirement, but may not have enough coil surface area to meet the discharge-air temperature requirement with 140°F heating-water supply (HWS) on a design heating day. To avoid upsizing to a three-row coil, it may be possible to provide an 8-in. terminal unit with a two-row coil. The cost of this upsize is minimal (10% to 20% of terminal box cost) and avoids the additional fan energy consumption required to overcome the increased pressure drop of a three-row coil. This additional cost is quickly offset via the efficiency gained by operating the condensing boilers at a higher efficiency range.

There are additional creative ways to drop the HWR temperature even further. Within a health care facility application, there are multiple systems that require heat with a consistent load profile that can serve as a heat sink for the HWR. These systems can include domestic hot-water heating, steam system make-up water preheating, snow-melt systems, and in-floor radiant heating systems. Each of the aforementioned systems can be intercepted and piped through individual plate-and-frame heat exchangers. The heating water can then be connected to the other sides of these heat exchangers, piped inline or in a side-stream configuration with three-way valves or inline pumps.

A simple example is the preheating of domestic cold water before it is sent to the domestic water heater. A conventional water heater will operate with similar efficiencies to that of a conventional boiler in the 80% to 85% efficiency range. Condensing water heaters are also available, which can operate in the same efficiency ranges as a condensing boiler (approximately 98%). However, efficiencies of a condensing water heater can be limited in part-load conditions due to the constant recirculation of hot water from the building and the intrinsic storage component of a water heater.

In a health care facility application at part-load conditions, domestic cold water between 40° to 60°F is mixed with water returning from the building between 110° and 120°F before entering the domestic water heaters. While this mixed temperature of water still allows condensation of water vapor in the flue gases for energy recovery, further efficiency can be gained if the make-up water is preheated by the HWR via a double-wall plate-and-frame heat exchanger. The water heaters are then used to boost the domestic hot water to a minimum temperature of 140°F, which is necessary to eliminate Legionella bacteria from building up in the hot-water system.

This system configuration maximizes the efficiency of the condensing boiler, whose operation is required regardless of the presence of the heat exchanger and, at minimum, limits and potentially eliminates firing of the condensing water heaters, which are operating a lower efficiency point. No equipment is more efficient than equipment that doesn't have to operate; this statement is not intended to discourage the use of a condensing water heater, but rather to place greater emphasis on system energy performance over component energy performance.

Implementation of an HWS temperature reset is also vital in reducing HWR temperature. In a traditional heating-water system with a fire- or water-tube boiler, the minimum limit that the supply heating-water temperature can reduce must be limited to prevent the HWR temperature from causing condensation in the flue and, in turn, damaging the boiler. In a condensing boiler system, there is no minimum limit and lower temperatures are encouraged.

Figure 1: Side-stream configuration of both the heat-recovery chiller and condensing water boilers maximizes the efficiency potential of both systems.


<< First < Previous Page 1 Page 2 Next > Last >>

Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me