Heat exchanger selection and optimization

The selection process is a trade-off between the overall heat transfer coefficient, which influences the pump head on the HVAC system.

10/28/2013


The selection process is a trade-off between the overall heat transfer coefficient (U), which has influence on the surface area, and pressure drop, which influences the pump head on the HVAC system. In general, low pressure drop increases the surface area of the heat exchanger, thereby increasing the unit’s initial cost, and the U value influences the type of chevron pattern plates to be used and pressure drop as well.

Table 1: Use this to calculate the surface area required for the heating and cooling load. Courtesy: Wallace Eannace Associates

See Table 1 to calculate the surface area required for the heating and cooling load.

Using the equations described in step 1, calculate the surface area required to perform the duties using the LMTD and NTU values for summer and winter conditions. Results of the calculation are shown in Tables 1 and 2.

Table 2: Surface area, NTU value, and pressure drop calculated for summer conditions. Courtesy: Wallace Eannace Associates

The key to selecting a heat exchanger is to select the smallest model with the same type of plate corrugation for both seasons (winter and summer) capable of handling the flow. 

Table 3: Surface area, NTU value, and pressure drop calculated for winter conditions. Courtesy: Wallace Eannace Associates

Next, simulate the heat exchanger with the largest surface area and plate corrugation type for the unit selected with the temperatures and flow profiles of the other season to obtain the duty value required for the season; see Table 4 for the heat exchanger solution. 

An optimal solution has been achieved when temperature, flow, and pressure drop are within the acceptable limits. 

Table 4: This shows the results of the simulated heat exchanger. Courtesy: Wallace Eannace Associates

Application notes:

Glycol system implications on the heat exchanger specification:

  • A glycol/water system affects the heat transfer of the heat exchanger and the pump noise.
  • Glycol does not carry heat as well as a water-only system.
  • Engineers must pay attention to the corresponding flow increase of glycol solution to maintain the minimum flow of the chiller and the corresponding pressure increase on the pump and pipe to prevent a noise problem.

Recommendation: Do not use chromate water treatments or galvanized fittings because they might react with the glycol solution. 


Jose R. Rodriguez is a technical services engineer with Wallace Eannace Assocs. where he has more than 15 years of experience in HVAC and plumbing. Mike Sammut, partner at AKF Group, has more than 30 years of experience in HVAC. Arslan Asovic is project engineer at AKF Group and has more than 10 years of experience in HVAC.



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
June 2018
Chilled-water system design, NFPA 99, Grounded power supply systems
May 2018
40 Under 40 winners, fire and life safety, performance-based designs, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me