Fan controls don't measure up

The fan controls at an airport terminal had never been reviewed, and needed to be updated with variable frequency drives.

12/27/2013


During a recent inspection of the HVAC systems for a 1-million-sq-ft airport terminal, the exp U.S. Services team noticed the installation of inlet vanes on about 35 of the variable air volume (VAV) air handlers. This seemed particularly odd because the fans were only about 10 years old.

When the engineering team inquired about the installation, the client indicated it was a cost issue and that at the installation time the inlet vanes were a cheaper control method than variable frequency drives (VFDs). It seems that a proper design review by the CxA would have addressed this issue, and perhaps suggested a lifecycle cost analysis (LCCA) to show the actual operating costs of using the inlet vane controls versus VFD controls.

The recommendation: replace the inlet vanes with VFDs. Although a moderately costly option, the annual savings are 2,360,000 kWh and $127,000. As a bonus, the state is offering incentives of about $160,000, so the effective payback is around 3.7 years.


Terrence Malloy is project manager for the energy solutions group at exp US Services Inc. He focuses on energy conservation, retro-commissioning, and renewable energy systems.



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
June 2018
Chilled-water system design, NFPA 99, Grounded power supply systems
May 2018
40 Under 40 winners, fire and life safety, performance-based designs, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me