Extended-surface filters compared to conventional filters

A MERV-11 extended-surface filter bank without a pre-filter was compared to a conventional 8-pocket MERV-11 filter with a MERV-4 prefilter.

09/16/2009


Extended surface Merv-11 filter performance was measured against conventional filters.
David Sellers, PE, senior engineer, Facility Dynamics Engineering, has reported measurements of rigid-pocket extended-surface Merv-11 filters with no prefilter. Baseline was a "fairly conventional" MERV 4 (ASHRAE Dust Spot Efficiency 20%) roll media type prefilter with a flexible 8 pocket MERV11 (ASHRAE dust spot efficiency 60-65%) bag fitler
The air handling systems are two virtually identical nominal 160,000 cfm double duct VAV units serving commercial office space in the Kaiser Permanente Building in Portland, Oregon.
His blog post has the details of the measurements and photos of the installations. Photos of the filter set up with dataloogers are provided along with plots of the performance data.

 





Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me