Empire State Building gets massive energy retrofit

A $20 million package of retrofits going into the Empire State Building in New York City will decrease energy use and carbon while increasing occupant comfort.

04/06/2009


Highlights: A $20 million package of retrofits going into the Empire State Building in New York City will decrease energy use and carbon while increasing occupant comfort. Upgrades include chillers, controls, ventilation, and glazing. The project team includes Johnson Controls, Rocky Mountain Institute, the Clinton Climate Initiative, and Jones Lang LaSalle. The energy savings should amount to $4.4 million per year and reduce energy use by 40%.

Using the Empire State Building as a test case and model, world-class environmental consulting, non-profit, design and construction partners %%MDASSML%% including the Clinton Climate Initiative (CCI), Rocky Mountain Institute (RMI), Johnson Controls Inc. (NYSE: JCI) (JCI) and Jones Lang LaSalle (NYSE: JLL) (JLL) %%MDASSML%% today unveiled an innovative process for analyzing and retrofitting existing structures for environmental sustainability.

 

Adopted as core elements of the more than $500 million upgrade program presently underway at the world’s most famous office building, the program is the first comprehensive approach that integrates many steps to use energy more productively.concluded by end of 2013. Work that is scheduled to be completed within 18 months will result in over 50 percent of the projected energy savings. The balance will be an additional 36 months completed by 2013.

 

The project will prove the viability for energy efficiency retrofit projects to dramatically increase building energy efficiency and reduce its overall carbon output with sensible payback periods and enhanced profitability.

 

At the end of the project definition process, the team analyzed the steps to be taken in conjunction with other steps towards sustainability as part of the Empire State ReBuilding program within the framework of the existing USGBC LEED rating system.

 

“Commercial and residential buildings account for the majority of the total carbon footprint of cities around the world %%MDASSML%% over 70 percent in New York City. Beginning in February 2008, the Empire State Building has been used as a test bench to create a replicable process to reduce energy consumption and environmental impacts,” said Anthony E. Malkin of building owner, Empire State Building Company.

 

“This innovative process, which has developed new techniques for modeling and organizing an integrated program, offers a clear path to adoption around the world, leading to significant reductions in greenhouse gas emissions,” according to Malkin.re sustainable operations %%MDASSML%% while simultaneously enhancing profitability and tenant comfort. This is a real program, happening in real time, creating real green jobs.” 

 

The project partners used existing and newly created modeling, measurement and projection tools in a new and repeatable process to analyze the Empire State Building and establish a full understanding of its energy use as well as its functional efficiencies and deficiencies.ntilation system upgrades and tenant space overhauls that will provide a significant return on investment, both environmentally and financially. 

 

“In this distressed economic climate, there is a tremendous opportunity for cities and building owners to retrofit existing buildings to save money and save energy,” said President Clinton. “I’m proud of the work my foundation's climate initiative has done with 40 of the world's largest cities, including New York where we played a central role in convening a unique set of partners that are working to make the Empire State Building retrofit project possible. It is this kind of innovative collaboration that is crucial to protecting our planet and getting our economy up and running again.”

 

“This project brings to bear every bit of experience, research and innovation we’ve accumulated in our 125 years in this business,” said Iain Campbell, Vice President, Johnson Controls, which serves as the energy services company for the program.

 

“Not only will this project dramatically reduce the Empire State Building’s environmental impact, but now we’re able to do it in a way that provides meaningful costs savings to the building as well as its tenants,” said Raymond Quartararo, International Director, Jones Lang LaSalle.

 

With an initial estimated project cost of $20 million, additional savings and redirection of expenditures originally planned in the building’s upgrade program, and additional alternative spending in tenant installations, the Empire State Building will save $4.4 million in annual energy savings costs, reduce its energy consumption by close to 40%, repay its net extra cost in about three years, and cut its overall carbon output through eight key initiatives, including:

 

1. Window Light Retrofit:

 

2. Radiator Insulation Retrofit:

 

3. Tenant Lighting, Daylighting and Plug Upgrades: Introduction of improved lighting designs, daylighting controls, and plug load occupancy sensors in common areas and tenant spaces to reduce electricity costs and cooling loads.

 

4. Air Handler Replacements: Replacement of air handling units with variable frequency drive fans to allow increased energy efficiency in operation while improving comfort for individual tenants.

 

5. Chiller Plant Retrofit: Reuse of existing chiller shells while removing and replacing “guts” to improve chiller efficiency and controllability, including the introduction of variable frequency drives.

 

6. Whole-Building Control System Upgrade: Upgrade of existing building control system to optimize HVAC operation as well as provide more detailed sub-metering information.

 

7. Ventilation Control Upgrade: Introduction of demand control ventilation in occupied spaces to improve air quality and reduce energy required to condition outside air.

 

8. Tenant Energy Management Systems:

 

Recently, several initiatives have been launched, including the CCI Building Retrofit program and New York City’s PlaNYC in 2007, which aim to reduce the significant carbon footprint of existing structures in major cities.aSalle, Rocky Mountain Institute, and Empire State Building Company, building owners now have a practical example of an economically intelligent path to be responsible members of the global community. This project can increase the confidence of cities, states and governments worldwide in the viability of programs that make positive changes, now.

 

“To make cities cleaner and more energy efficient, we urgently need a replicable model for retrofitting existing major buildings.

 

The full analysis process is available online as open-source materials for public use at www.esbsustainability.com and www.esbnyc.com .

 

About the Clinton Climate Initiative

The William J. Clinton Foundation launched the Clinton Climate Initiative (CCI) to create and advance solutions to the core issues driving climate change. Working with governments and businesses around the world to tailor local solutions that are economically and environmentally sustainable, CCI focuses on three strategic program areas: increasing energy efficiency in cities, catalyzing the large-scale supply of clean energy, and working to measure and value the carbon absorbed by forests.efforts to reduce greenhouse gas emissions, and of which New York is a member. To learn more about the work of the Clinton Climate Initiative and the William J. Clinton Foundation, please visit www.clintonfoundation.org .

Contact: press@clintonfoundation.org

 

About Johnson Controls Inc.

Johnson Controls (NYSE: JCI) is the global leader that brings ingenuity to the places where people live, work and travel. By integrating technologies, products and services, we create smart environments that redefine the relationships between people and their surroundings. Our team of 140,000 employees creates a more comfortable, safe and sustainable world through our products and services for more than 200 million vehicles, 12 million homes and one million commercial buildings. Our commitment to sustainability drives our environmental stewardship, good corporate citizenship in our workplaces and communities, and the products and services we provide to customers. For additional information, please visit www.johnsoncontrols.com .

Contact:

 

About Jones Lang LaSalle

Jones Lang LaSalle (NYSE:JLL) is a financial and professional services firm specializing in real estate. The firm offers integrated services delivered by expert teams worldwide to clients seeking increased value by owning, occupying or investing in real estate. With 2008 global revenue of $2.7 billion, Jones Lang LaSalle serves clients in 60 countries from 750 locations worldwide, including 180 corporate offices.l estate with more than $46 billion of assets under management. For further information, please visit our Web site, www.joneslanglasalle.com .

Contact:

 

About Rocky Mountain Institute

Rocky Mountain Institute (RMI), a 501(c)(3) nonprofit organization, was established in 1982 by resource analysts L. Hunter Lovins and Amory B. Lovins. What began as a small group of colleagues focusing on energy policy has since grown into a broad-based institution with approximately eighty full-time staff, an annual budget of nearly $12 million (over half of it earned through programmatic enterprise), and a global reach.

Contact:

 

About Empire State Building

The “World’s Most Famous Office Building,” the Empire State Building is in the midst of the more than $500 million Empire State ReBuilding program as the flagship of the W&H Properties portfolio of Pre-War Trophy office buildings. Since the Empire State ReBuilding program began in 2007, new investments in infrastructure, public areas and amenities have attracted new, first-rate tenants in a diverse array of industries from around the world.Observatory is the region’s #1 tourist destination. For more information on the Empire State Building, please visit www.esbnyc.com .

Contact: Adam Pietrala, 212-704-8176, adam.pietrala@edelman.com; Viet N’Guyen, 212-704-4535, viet.n’guyen@edelman.com

 





Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me