Electrical fire pump with emergency generator

In this case study, an onsite generator must provide the secondary source of power for the fire pump.

03/24/2016


Figure 2: Power feed to the fire pump is shown via a direct connection from a utility transformer. Courtesy: WSP + ccrdThe building's normal power service is supplied from a pad-mounted utility transformer that is fed by a singular utility substation. The authority having jurisdiction has deemed that the single utility service is not considered a reliable source, so it cannot be the only supply source for the fire pump. An onsite generator must provide the secondary source of power for the fire pump. The service to the fire pump will need to meet the requirements as defined by NFPA 70: National Electrical Code (NEC) 695.3(B)(2) for service from an individual source and onsite standby generator.

The primary supply to the fire pump controller will come directly from a connection at the utility transformer. This was coordinated with the utility company; most will allow for this separate connection to be tapped at the transformer. This meets the requirement for continuity of power as defined by NEC 695.4(A) (direct connection). The feeder from the switchgear to the fire pump controller (located in a different area) will be routed below the building floor slab so that it is considered outside the building per NEC 230.6(1).

The second source for the fire pump will come from the emergency power system for the building. The building's generator system will be sized to handle the starting and normal operating load of the fire pump as defined by NED 695.3(D)(1). A circuit breaker, sized to accommodate normal start-up of the pump, will be located in the emergency distribution board. The second feeder will route overhead to the fire pump controller and be encased in a minimum of 2-in. concrete.

 


Sarah Kuchera is senior vice president and electrical engineer at ccrd + WSP. Her duties have included project management, production coordination, and project engineering on a variety of different projects including hospital, retail, hospitality, and office buildings. 



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me