Distribution vs. Transmission: Comparing Tariffs

Larger industrial and commercial building owners can restructure their electric service to best take advantage of the deregulated environment. The end-user can select a preferred generation source, and, in effect, use the electric transmission system as a common carrier to get energy to his facility, bypassing altogether the local utility's distribution system.

11/01/2000


Larger industrial and commercial building owners can restructure their electric service to best take advantage of the deregulated environment. The end-user can select a preferred generation source, and, in effect, use the electric transmission system as a common carrier to get energy to his facility, bypassing altogether the local utility's distribution system.

The decision to bypass the distribution system is primarily economic. Transmission service is generally much less expensive, and having choice implies competition on price.

However, to have access to the interconnected utility grid and multiple generation providers, the end-user's electric service must migrate from the serving utility's distribution system to the transmission system. Also, the industrial facility must assume all of the design and operational responsibilities traditionally handled by the utility.

To assist in determining whether the additional work is worth the savings, it helps to quantify them. The attached tables, which compare the distribution and transmission tariffs from a large Midwestern utility, show a typical industrial load using both tariffs, as well as the percentage savings for sample load ranges and load factors.

Table 1 - Typical Tariffs and Industrial Load Calculations


TYPICAL TARIFFSDistribution serviceTransmission service

Service charge

$10.00

$100.00

Demand charge

First 1,000 kW: 12.11 per kW

First 50,000 kVA: 10.53 per kVA

Additional demand: 10.51 per kW

Additional demand: 8.19 per kVA

Energy charge

Demand times 300: 0.01905 per kWh

Demand times 300: 0.0085 per kWh

Additional kWh: 0.00720 per kWh

Additional kWh: 0.0067 per kWh

INDUSTRIAL EXAMPLE

Distribution service

Transmission service

Service charge

$10.00

$100.00

Demand charge

1,000 kW X $12.11 = $12,110.00

3,500 kW X $10.53 = $368,550.00

34,000 kW X$10.51 = $357,340.00

Energy charge

35,000 X 300 = 10,500,000 X 0.01905 = $200,025.00

35,000 X 300 = 10,500,000 X 0.0085 = $89,250.00

(17,885,000-10,500,000) X $0.0072 = $53,172.00

(17,885,000-10,500,000) X $0.0067 = $49,479.00

Total

$622,657

$507,379


Transmission tariffs from a large Midwestern utility show that they are generally much cheaper than distribution rates. An industrial facility with a 35,000-kW load and a monthly energy consumption of 17,885,000 kWh-and a load factor of 70 percent-will have the charges shown above (fuel charge excluded) at 100-percent power factor.

Table 2 - Savings


Load (Kw)Savings (%)

10,000

19.0

20,000

18.7

30,000

18.5

40,000

18.5

50,000

18.5

60,000

18.4

70,000

18.4

80,000

18.4

90,000

18.4

100,000

18.4


Using the tariffs shown in Table 1, potential savings were calculated over a broad range of demands, showing a consistent level of savings. Another major variable to consider is load factor, which is found by dividing the total annual energy consumed by the demand, multiplied by 8,760 hours per year. The lower values shown represent peak loads.

Table 3 - Load Factor


Load Factor (%)Savings (%)

0.5

19.2

0.55

19.1

0.6

18.9

0.65

18.7

0.7

18.5

0.75

18.3

0.8

18.2

0.85

18.0

0.9

17.9

0.95

17.7

1

17.6





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me