Controlling Condensation with the Right Insulation

Changes in one type of technology often make changes in related technologies necessary. For example, about a half-decade ago, facilities began running their chilled-water systems colder in an effort to reduce piping size and the required pumping power. While many engineers embraced this philosophy, it presented a new problem—condensation, especially in places like the southeastern United ...

06/01/2004


Changes in one type of technology often make changes in related technologies necessary.

For example, about a half-decade ago, facilities began running their chilled-water systems colder in an effort to reduce piping size and the required pumping power. While many engineers embraced this philosophy, it presented a new problem—condensation, especially in places like the southeastern United States. This condensation can lead to problems such as dripping, saturation of the insulation and mold growth.

Chuck Crim, Toledo, Ohio-based specification manager with Owens Corning, offers several suggestions. First, he stresses the importance of being familiar with the specific design criteria, temperature and relative humidity for the job location. "An engineer has got to know that they can't make assumptions that are incorrect, because if they specify a certain thickness based on an assumption and they're incorrect, they're going to have a problem," he says.

To elaborate, Crim explains that K values vary for different types of insulation. For example, fiberglass insulation has a K value of .23, while cellular glass has a K value of .33. As such, the thermal efficiency of an arbitrary insulation thickness—1.5 in., for example—will vary based on the type of insulation used.

Crim also stresses the need to understand the shortcomings of traditional methodologies, the danger of improperly installed joints and elbows and the possibility of damage to the jacket by other trades. "The insulator can go in there and do his job very well, and then you have a plumber or electrician who comes in and sticks his screwdriver in the insulation as a holder, and he's broken the vapor barrier." he explains.

Yet another issue to consider is whether the chilled-water system will be running prior to installation of the insulation. As insulation needs to be installed when the pipes are completely dry, the system must be shut down to allow any moisture to evaporate. This becomes a problem not only with retrofit projects, but also with new construction, as facility managers will often turn the system on to dry out the building prior to insulating. "And the question is, then, can you afford to shut the system down, dry the piping out, apply the insulation, then turn the system back on? In most cases, they either can't or won't do that," Crim says.

However, Crim points to an Owens Corning technology that can render these last two considerations irrelevant. Because moisture will almost always find some way to permeate insulation, the company developed VaporWick, a breathable, self-drying piping insulation system that allows the moisture to leave the area via a wick and evaporate into the ambient air, thus keeping the piping dry and factoring out condensation. As such, while the insulation uses a traditional fiberglass-based jacket, it doesn't rely on that jacket—or the installer's expertise.



Piping Insulation Suggestions

Be mindful of damage to insulation jacket by other trades

Familiarize yourself with a project location's design criteria, temperature and relative humidity

Don't select an arbitrary thickness; choose insulation thickness based on K value



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
October 2018
Approaches to building engineering, 2018 Commissioning Giants, integrated project delivery, improving construction efficiency, an IPD primer, collaborative projects, NFPA 13 sprinkler systems.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me