Condensing boilers and emissions regulations

For this Shippensburg University boiler replacement project, major consideration was given to local codes, space requirements, boiler control, and emission reductions.

12/29/2014


During the replacement of an aging central steam plant at Shippensburg University (S.U.) in Shippensburg, Pa., the operating efficiency and sustainability depended on careful selection and specification of condensing hot water boilers. Fire tubes condensing boilers are used in the new heating plant design.

To select the most appropriate boiler, the engineer must considered the following specifications: local code requirements, cost impact, emission regulations, floor space, boiler control, boiler heat exchanger, flue material and location, drain required, hot water return temperature, minimum flow to the boiler, operating weight of the equipment, heating coil requirements, warranty coverage, and service personnel available in the area. The engineer also must consider high turndown of the boiler, because it might reduce short cycling when demand is low. If the boiler meets the actual system demand, it can reduce fuel cost for the building owner.

For this project, major consideration was given to local codes, space requirements, boiler control, and emission reductions. In 2007, Pennsylvania State Code section IV HG-716 for modular boilers stated that side-by-side installation boilers are acceptable to a maximum of 400 MBh capacity. The only way to install the boilers at the facility was to engage the boiler manufacturer to work together with the Pennsylvania Code Authority, allowing variance approval, before the units could be installed.

The low NOx requirement began with the comprehensive South Coast Air Quality Management District (SCAQMD) program from Southern California, which is used in most of the country.

The boiler industry faces more stringent NOx emission regulations from the EPA. For boilers greater than 2000 MBh, a third-party test is required and NOx should be below 9 ppm. Annual inspections are required as well.

In 2011, the EPA issued a new regulation for boiler maximum achievable control technology, known as MACT. This rule is known as the National Emission Standard for Hazardous Air Pollutants (NESHAP).

To determine the emission limits for NESHAP, EPA and PA DEP use the MACT approach; the regulation was effective in 2012.

The NESHAP regulations define an area source of air emissions as any stationary source or group of stationary sources that annually emit in aggregate less than 10 tons of any single hazardous air pollutant (HAP) or less than 25 tons of multiple HAPs.

Existing coal-fired boilers with a heat input equal or greater than 10 million Btuh are required to adhere to emission limits for mercury and carbon monoxide.

This new regulation determines what a boiler’s emissions are and how often the boiler must be tuned up, based on its size and type. Existing central heating plants do not meet this requirement, and operating an existing central heating plant at the university could be quite costly.


Andre Pearson is lead engineer, infrastructure and optimization at WM Group. Pearson has 11 years of experience in HVAC design, energy audit, and commissioning services for various market sectors. He has completed numerous systems assessments/optimization projects and has identified millions of dollars in savings combined with improved reliability. Jose R. Rodriguez is a technical service engineer at Wallace Eannace Associates Inc. Rodriguez assists engineering consulting firms in New York City on the HVAC product segment of the company.



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
November 2018
Emergency power requirements, salary survey results, lighting controls, fire pumps, healthcare facilities, and more
October 2018
Approaches to building engineering, 2018 Commissioning Giants, integrated project delivery, improving construction efficiency, an IPD primer, collaborative projects, NFPA 13 sprinkler systems.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me