Commissioning Smoke-Control Systems

Commissioning and acceptance testing demonstrate that the final integrated system complies with the design and that any modifications were correctly and successfully incorporated, so that the result is a properly functioning system. The design engineer must be involved with the test-and-balance contractor, the mechanical contractor, electrical contractor, controls vendor and fire-alarm vendor.

01/01/2001


Commissioning and acceptance testing demonstrate that the final integrated system complies with the design and that any modifications were correctly and successfully incorporated, so that the result is a properly functioning system. The design engineer must be involved with the test-and-balance contractor, the mechanical contractor, electrical contractor, controls vendor and fire-alarm vendor. Each component must be verified for operation, including:

  • Pressure differences. Differentials must be taken across every door and recorded.

 

  • Shutdown of air systems and damper closure. This sequence must take place with the correct initiation.

 

  • Restart. The system must restart automatically upon fire-alarm reset

Accessible openings in outside-air and return-air ducts must be installed so that actual automatic damper position can be observed. Relying on the damper-shaft indicating notch is an invitation to trouble. The owner's engineering staff and maintenance personnel must be instructed-not only in the operation but in the design intent of a facility so that an understanding of systems operation is achieved.





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
June 2018
Chilled-water system design, NFPA 99, Grounded power supply systems
May 2018
40 Under 40 winners, fire and life safety, performance-based designs, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me